Solar System Design Guide
39
6020 457 - 01
Manual Air Vent Valve
Locking ring fitting with manual air vent valve.
For installation at the highest point of the system.
Can be used as an alternative to a fast acting air vent.
Installation in the supply pipe of the solar circuit,
preferably upstream of the inlet into the DHW tank.
With shut-off valve and locking ring fitting. Install one
fast acting air vent valve in each collector array, and at
the highest point of the system.
Stainless steel corrugated pipes with thermal insulation
and protective foil, locking ring fittings and sensor wire.
Available in three coil sizes:
– 20 ft. (6 m) long
– 40 ft. (12 m) long
– 50 ft. (15 m) long
Air Separator
(with shut-off)
Fast-acting Air Vent Valve
(with shut-off)
Flexible Insulated Piping
For use in smaller scale solar systems having up to four
Vitosol 200-FM collectors. Refer to pressure drop chart on
page 73.
IMPORTANT
Shut-off valve must be closed after initial system
commissioning. Failure to close will result in glycol
steaming off during stagnation.
Installation Accessories