Solar System Design Guide
81
6020 457 - 01
System Fluid Calculator
Solar Components
Quantity
Liquid Content
Total Liquid Content
USG
(L)
USG
(L)
Miscellaneous fluid content
1
x
0.80
(3.00)
=
0.80
(3.00)
Vitosol 200-FM, SV2F
x
0.48
(1.83)
=
Vitosol 200-FM, SH2F
x
0.66
(2.48)
=
Solar-Divicon, DN20B
x
0.11
(0.40)
=
Solar-Divicon, DN25B
x
0.20
(0.75)
=
Solar-Divicon-HX, DN20
x
0.26
(0.98)
=
Vitocell 300-W, EVIA - 42 USG (160 L)
x
1.96
(7.40)
=
Vitocell 300-V, EVIA - 53 USG (200 L)
x
1.96
(7.40)
=
Vitocell 300-V, EVIA - 79 USG (300 L)
x
2.91
(11.00) =
Vitocell 300-V, EVIB - 119 USG (450 L)
x
3.43
(13.00) =
Vitocell 300-B, EVBA - 79 USG (300 L)
x
2.91
(11.00) =
Vitocell 300-B, EVBB - 119 USG (450 L)
x
3.43
(13.00) =
Vitocell 300-H, EHA - 92 USG (350 L)
x
3.43
(13.00) =
Vitocell 300-H, EHA - 119 USG (450 L)
x
4.23
(16.00) =
Other:
x
=
Other:
x
=
Other:
x
=
Other:
x
=
Solar Piping
Total Length
Liquid Content
Total Liquid Content
(select the following pipe size or combination of sizes)
ft
(m)
USG/ft
(L/m)
USG
(L)
b
” Copper, Type-L (5/8” O.D.)
x
0.012
(0.15)
=
c
” Copper, Type-L (7/8” O.D.)
x
0.025
(0.31)
=
1” Copper, Type-L (1-1/8” O.D.)
x
0.044
(0.55)
=
1
a
” Copper, Type-L (1-3/8” O.D.)
x
0.066
(0.81)
=
1
b
” Copper, Type-L (1-5/8” O.D.)
x
0.093
(1.15)
=
½” Stainless Steel Insulated Lineset *
x
0.020
(0.25)
=
1/2” Sch-40 Steel Pipe
x
0.016
(0.20)
=
3/4” Sch-40 Steel Pipe
x
0.028
(0.34)
=
1” Sch-40 Steel Pipe
x
0.045
(0.56)
=
1-1/4” Sch-40 Steel Pipe
x
0.077
(0.96)
=
1-1/2” Sch-40 Steel Pipe
x
0.106
(1.32)
=
Total Liquid Content of System
(Solar Comp Solar Piping)
Note:
Use this table to calculate the required amount of liquid content required for the solar thermal system.
1) Input the quantities for each listed item and the length of piping (in feet or meters) used in the system. Then multiply
each item by the liquid content listed for each item and input each item total in the Total Liquid Content column.
2) Add all of the individual liquid content totals to determine the total liquid content of the system.
* This lineset comes in 20 ft., 40 ft. and 50 ft. lengths (it combines two pipes for supply and return wrapped in
foam insulation). Example: A 20 ft. piping kit contains 20 ft. of supply and 20 ft. of return having a total length of 40 ft.
Design and Operation