Coding in the delivered condition
Possible change
F8:-5
Temperature limit for
terminating the reduced
mode -5 ºC, see exam-
ple on page 91.
Observe the setting of
coding address "A3".
F8:+10
to
F8:-60
Temperature limit adjus-
table from
+10 to -60 °C
F8:-61
Function disabled
F9:-14
Temperature limit for
raising the reduced set
room temp. -14 ºC, see
example on page 91.
F9:+10
to
F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjus-
table from
+10 to -60 °C
FA:20
Raising the set boiler
water temperature or
the set flow temperature
when changing from op-
eration with reduced
room temperature to op-
eration with standard
room temperature, by
20 %. See example on
page 92.
FA:0
to
FA:50
Temperature rise adjusta-
ble from 0 to 50 %
Fb:30
Duration for raising the
set boiler water tem-
perature or the set flow
temperature (see cod-
ing address "FA")
60 min. See example on
page 92.
Fb:0
to
Fb:150
Duration adjustable from
0 to 300 min;
1 step
≙
2 min
Resetting codes to their delivered condition
Press the following keys:
1.
L
+
G
simultaneously for
approx. 2 s.
2.
e
"
Standard setting?
Yes
" appears.
3.
d
to confirm
or
4.
a
/
b
to select "
Standard set-
ting? No
".
Code 2
(cont.)
60
Coding
5692
779
GB
Summary of Contents for VITOLADENS333-F
Page 101: ...Parts lists cont 101 Parts lists 5692 779 GB...
Page 102: ...Parts lists cont 102 Parts lists 5692 779 GB...
Page 103: ...Parts lists cont 103 Parts lists 5692 779 GB...
Page 104: ...Parts lists cont 104 Parts lists 5692 779 GB...
Page 105: ...Parts lists cont 105 Parts lists 5692 779 GB...