Coding in the delivered condition
Possible change
71:0
DHW circulation pump:
"ON" according to time
program
71:1
"OFF" during DHW heat-
ing to the first set value
71:2
"ON" during DHW heat-
ing to the first set value
72:0
DHW circulation pump:
"ON" according to time
program
72:1
"OFF" during DHW heat-
ing to the second set
value
72:2
"ON" during DHW heat-
ing to the second set
value
73:0
DHW circulation pump:
"ON" according to time
program
73:1
to
73:6
During the time program
"ON" 1x/h for 5 min
"ON" up to 6x/h for 5 min
73:7
permanently "ON"
General
76:0
Without LON communi-
cation module
76:1
With LON communication
module (automatic recog-
nition)
77 :1
LON subscriber number 77 :2
to
77 :99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only
once.
79:1
With LON communica-
tion module: Control
unit is fault manager
79:0
Control unit is not fault
manager
7b:1
With LON communica-
tion module: Control
unit transmits the time
7b:0
Do not transmit time
7F:1
Detached house
7F:0
Apartment block
Separate adjustment of
holiday program and time
program for DHW heat-
ing, as option
Code 2
(cont.)
51
Coding
5692
779
GB
Summary of Contents for VITOLADENS333-F
Page 101: ...Parts lists cont 101 Parts lists 5692 779 GB...
Page 102: ...Parts lists cont 102 Parts lists 5692 779 GB...
Page 103: ...Parts lists cont 103 Parts lists 5692 779 GB...
Page 104: ...Parts lists cont 104 Parts lists 5692 779 GB...
Page 105: ...Parts lists cont 105 Parts lists 5692 779 GB...