Adjusting the set room temperature
Standard room temperature
Example 1: Adjustment of standard
room temperature from 20 to 26 °C
A
Boiler water temperature or flow
temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Press the following keys:
1.
a
"1
r
" flashes.
2.
d
to select heating circuit A1
(heating circuit without mixer)
or
3.
a
"2
r
" flashes.
4.
d
to select heating circuit with
mixer M2.
5.
Adjust the set day temperature with
rotary selector "
ts
".
The value will be automatically
accepted after approx. 2 s.
Accordingly, the heating curve is
adjusted along set room tempera-
ture axis
C
, which results in modi-
fied start/stop characteristics of the
heating circuit pumps if heating cir-
cuit pump logic function is active.
Reduced room temperature
Example 2: Adjustment of reduced
room temperature from 5 °C to 14 °C
A
Boiler water temperature or flow
temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Press the following keys:
1.
a
"1
r
" flashes.
Further details regarding the individual steps
(cont.)
38
Commissioning, inspection, maintenance
5692
779
GB
Summary of Contents for VITOLADENS333-F
Page 101: ...Parts lists cont 101 Parts lists 5692 779 GB...
Page 102: ...Parts lists cont 102 Parts lists 5692 779 GB...
Page 103: ...Parts lists cont 103 Parts lists 5692 779 GB...
Page 104: ...Parts lists cont 104 Parts lists 5692 779 GB...
Page 105: ...Parts lists cont 105 Parts lists 5692 779 GB...