![Viessmann VITOGAS Technical Manual Download Page 32](http://html.mh-extra.com/html/viessmann/vitogas/vitogas_technical-manual_1017321032.webp)
Performance factor N
L
to DIN 4708
Cylinder storage temperature T
cyl
= cold water inlet tempe50 K
+5 K/-0 K
Cylinder capacity
litres
160
200
350
500
Performance factor N
L
at heating water flow temperature
90 °C
2.3
6.6
12.0
23.5
80 °C
2.2
5.0
12.0
21.5
70 °C
1.8
3.4
10.5
19.0
Performance factor N
L
The performance factor N
L
varies according to the cylinder storage
temperature T
cyl
.
Standard values
■ T
cyl
= 60 °C
→
1.0 × N
L
■ T
cyl
= 55 °C
→
0.75 × N
L
■ T
cyl
= 50 °C
→
0.55 × N
L
■ T
cyl
= 45 °C
→
0.3 × N
L
Peak output (over 10 minutes)
Based on performance factor N
L
DHW heating from 10 to 45 °C
Cylinder capacity
litres
160
200
350
500
Peak output
(litres/10 minutes)
at heating water flow temperature
90 °C
203
335
455
660
80 °C
199
290
445
627
70 °C
182
240
424
583
Max. draw-off rate (over 10 minutes)
Based on performance factor N
L
With booster
DHW heating from 10 to 45 °C
Cylinder capacity
litres
160
200
350
500
Max. draw-off rate
(litres/minute)
at heating water flow temperature
90 °C
20
33
45
66
80 °C
20
29
45
62
70 °C
18
24
42
58
Available water volume
Cylinder volume heated to 60 °C
Without booster
Cylinder capacity
litres
160
200
350
500
Draw-off rate
l/min
10
10
15
15
Available water volume
Water with t = 60 °C (constant)
litres
150
185
315
440
Heat-up time
The heat-up times specified will be achieved subject to the maximum
continuous output of the DHW cylinder being made available at the
relevant flow temperature and when DHW is heated from 10 to
60 °C.
Cylinder capacity
litres
160
200
350
500
Heat-up time
(minutes)
at heating water flow temperature
90 °C
19
18
15
20
80 °C
26
25
20
26
70 °C
34
32
31
40
DHW cylinder
(cont.)
32
VIESMANN
VITOGAS
3
5822 428 GB