![Viessmann VITOGAS Technical Manual Download Page 30](http://html.mh-extra.com/html/viessmann/vitogas/vitogas_technical-manual_1017321030.webp)
3.4 Specification Vitocell 300-H, type EHA
For DHW heating
in conjunction with boilers, district heating systems
and low temperature heating systems
Suitable for systems with
■ Heating water flow temperature up to
200 °C
■ operating pressure on the
heating water side
up to
25 bar
or
satu-
rated steam
with
1 bar
positive pressure
■ operating pressure on the
DHW side
up to
10 bar
Cylinder capacity
litres
160
200
350
500
DIN register number
0081/08-10 MC
Continuous output
for DHW heating from
10 to
45 °C
and a
heating water
flow
temperature of ... at the heating
water throughput stated below
90 °C
kW
32
41
80
97
l/h
786
1007
1966
2383
80 °C
kW
28
30
64
76
l/h
688
737
1573
1867
70 °C
kW
20
23
47
55
l/h
490
565
1155
1351
65 °C
kW
17
19
40
46
l/h
417
467
983
1130
60 °C
kW
14
16
33
38
l/h
344
393
811
934
Continuous output
for DHW heating from
10 to
60 °C
and a
heating water
flow
temperature of ... at the heating
water throughput stated below
90 °C
kW
28
33
70
82
l/h
482
568
1204
1410
80 °C
kW
23
25
51
62
l/h
396
430
877
1066
70 °C
kW
15
17
34
39
l/h
258
292
585
671
Heating water throughput
for the stated continuous outputs
m
3
/h
3.0
5.0
5.0
5.0
Continuous output
for DHW heating from
10 to
45 °C
and
saturated steam
from ... with a max. steam veloc-
ity of 50 m/s
0.5 bar
kW
–
–
83
83
l/h
2039
2039
1.0 bar
kW
–
–
105
105
l/h
2580
2580
Standby heat loss
q
BS
at 45 K tempera-
ture differential (actual values to
DIN 4753-8)
kWh/24 h
1.20
1.30
1.90
2.30
Overall dimensions
Total length
mm
1072
1236
1590
1654
Total width
mm
640
640
830
910
Width without casing
mm
–
–
768
810
Total height
mm
654
654
786
886
Weight
DHW cylinder with thermal insulation
kg
76
84
172
191
Heating water content
litres
7
8
13
16
Heating surface
m
2
0.87
0.9
1.7
2.1
Connections
Heating water flow and return
R
1
1
1¼
1¼
Cold water, hot water
R
¾
¾
1¼
1¼
DHW circulation
R
1
1
1
1¼
Information on width without casing (350 and 500 litres)
350 litre: Where access into the boiler room is difficult, the front panel
with thermometer and the side panels can be removed, the
adjustable feet can be unscrewed and the DHW cylinder can
be turned to one side.
500 litre: Where access to the boiler room is difficult, removal of the
casing leaves the DHW cylinder with only the dimensions
given in the table.
Information regarding continuous output
When designing the system for the continuous output as stated or cal-
culated, allow for the corresponding circulation pump. The stated con-
tinuous output is only achieved when the rated boiler output
≥
contin-
uous output.
DHW cylinder
(cont.)
30
VIESMANN
VITOGAS
3
5822 428 GB