2.
Connect the hydraulic lines.
System with 1 heating circuit:
■
Connect the heating return to boiler return 1.
System with 2 heating circuits:
■
Connect the heating circuit with the higher tem-
perature level to boiler return 2.
■
Connect at least 15 % of the rated heating output
to boiler return 1.
!
Please note
Mechanically loaded hydraulic connections
lead to leaks, vibrations and appliance dam-
age.
Connect on-site lines so that they are free of
load and torque stress.
3.
Seal any unused connections.
Note
Never connect a heat consumer to connector
D
(safety connection).
4.
Check the hydraulic connections for tightness.
!
Please note
Unsuitable water quality can damage the
boiler body.
Only fill the boiler with water that complies
with the "Water quality requirements": See
"Vitocrossal, type CRU" service instructions
5.
Thermally insulate the hydraulic lines.
Connections on the heating water side
(cont.)