60
Coding in the delivered condition
Possible change
F2:8
Time limit for party mode
8 hours or external heat-
ing program changeover
via the keyboard (only for
weather-compensated
control units)
*1
F2:0
No time limit for party mode
F2:1
to
F2:12
Time limit adjustable from 1
to 12 hours
*1
F5:12
Run-on time of the circu-
lation pump in the heating
circuit connection set in
heating mode 12 min
(only for constant temper-
ature control units)
F5:0
No run-on time for the cir-
culation pump in the heat-
ing circuit connection set
F5:1
to
F5:20
Run-on time of the circula-
tion pump in the heating cir-
cuit connection set adjust-
able from 1 to 20 min
F6:25
In the "DHW only" oper-
ating mode, the circula-
tion pump in the heating
circuit connection set is
permanently ON (only for
constant temperature
control units)
F6:0
In the "DHW only" operat-
ing mode, the circulation
pump in the heating circuit
connection set is perma-
nently OFF
F6:1
to
F6:24
In the "DHW only" operat-
ing mode, the circulation
pump in the heating circuit
connection set will be star-
ted 1 to 24 times per day for
10 min respectively
F7:25
In the "Standby" operat-
ing mode, the circulation
pump in the heating cir-
cuit connection set is per-
manently ON (only for
constant temperature
control units)
F7:0
In the "Standby" operating
mode, the circulation pump
in the heating circuit con-
nection set is permanently
OFF
F7:1
to
F7:24
In the "Standby" operating
mode, the circulation pump
in the heating circuit con-
nection set will be started 1
to 24 times per day for
10 min respectively
*1
Party mode ends automatically in heating program "
rw
" when the system
changes over to operation with standard room temperature.
Codes
Code 2
(cont.)
5692 760 GB