50
Coding in the delivered condition
Possible change
General
76:0
Without LON communi-
cation module (only for
weather-compensated
control units)
76:1
With LON communication
module; automatic recog-
nition
76:2
With KM BUS/cascade
communication module;
automatic recognition
77 :1
LON subscriber number
(only for weather-com-
pensated control units)
77 :2
to
77 :99
LON subscriber number,
adjustable from 1 to 99
(see page 34).
Note
Allocate each number
only once.
79:1
With LON communication
module: Control unit is
fault manager (only for
weather-compensated
control units)
79:0
Control unit is not fault
manager
7b:1
With LON communication
module: The control unit
transmits the time (only
for weather-compensa-
ted control units)
7b:0
Do not transmit time
7F:1
Detached house (only for
weather-compensated
control units)
7F:0
Apartment block
Separate adjustment of
holiday program and time
program for DHW heating,
as option
80:1
A fault message is dis-
played, providing a fault
is active for at least 5 s
80:0
Immediate fault message
80:2
to
80:199
The fault message is
issued after a delay that is
adjustable from 10 s to
995 s; 1 step = 5 s
Codes
Code 2
(cont.)
5692 760 GB