Initial start−up, inspection and maintenance

Inspection and maintenance 

(cont.)

Cleaning the inside of DHW cylinders

1.

Drain the DHW cylinder from the
secondary side.

2.

Remove top panel

A

, thermal

insulation mat

B

 and

thermometer sensor

C

.

3.

Remove locking cap

D

, internal,

circular stainless steel disc

E

 and

gasket

F

.

4.

Disconnect the DHW cylinder
from the pipework to prevent any
cleaning agents and contaminants
entering the pipe system.

5.

Remove loose deposits with a
high pressure cleaner.

¨

Only use plastic tools to clean
the inside.

6.

Use a chemical cleaning agent 
to remove hard deposits that
cannot be removed by a high
pressure cleaner.

¨

Safety instructions

Do not use cleaning agents
containing hydrochloric acid.

7.

Thoroughly flush the DHW
cylinder after cleaning.

8.

Reconnect the DHW cylinder to
the pipework.

9.

A new gasket

F

 must be fitted

to locking cap

D

 every time the

cylinder is opened.

10.

Fit circular stainless steel disc

E

,

locking cap

D

 and tighten down

with 160Nm.

11.

Fill the DHW cylinder from the
secondary side.

12.

Fit thermometer sensor

C

,

thermal insulation mat

B

 and

top panel

A

.

System restart

5692328GB

D

F

E

B

A

C

Summary of Contents for VITOCELLV 300

Page 1: ...VITOCELL V 300 VITOCELL W 300 Service instructions for heating engineers Vitocell V 300 and Vitocell W 300 Type EVA DHW cylinders 130 to 200 litres capacity 5692 328 GB 12 2003 Please keep safe ...

Page 2: ...nt parts that have been approved by Viessmann Initial start up The system must be commissioned by the system installer or a qualified person authorised by the installer Instructing the system user The system installer must hand the operating instructions to the system user and instruct him her in the operation of the system Safety instructions In this instruction manual this heading denotes inform...

Page 3: ...mpression fittings on the primary and secondary side for leaks and retighten if necessary 3 Check the function of safety valves according to manufacturer s instructions Inspection and maintenance In Germany DIN 1988 requires a visual inspection and if necessary cleaning no later than two years after the cylinder has been taken into use and thereafter according to demand System shutdown Checking el...

Page 4: ... high pressure cleaner Only use plastic tools to clean the inside 6 Use a chemical cleaning agent to remove hard deposits that cannot be removed by a high pressure cleaner Safety instructions Do not use cleaning agents containing hydrochloric acid 7 Thoroughly flush the DHW cylinder after cleaning 8 Reconnect the DHW cylinder to the pipework 9 A new gasket F must be fitted to locking cap D every t...

Page 5: ...002 Top insulating mat 003 Sensor retaining clip 004 Sensor retainer 005 Cylinder locking cap with item 006 and 007 006 Circular stainless steel disc with item 007 007 Gasket 008 Adjustable foot 010 Thermometer 012 Vitocell 300 logo 013 Centering sleeve Parts not shown 015 Installation instructions 018 Service instructions 019 Spray paint 020 Paint stick A Type plate 5692 328 GB 013 A 007 006 005 ...

Page 6: ...6 Parts list 5692 328 GB ...

Page 7: ...ice date by Maintenance service Maintenance service Maintenance service date by Maintenance service Maintenance service Maintenance service date by Maintenance service Maintenance service Maintenance service date by Maintenance service Maintenance service Maintenance service date by 5692 328 GB ...

Page 8: ...fo uk viessmann com 8 Appendix Applicability Vitocell V 300 and Vitocell W 300 type EVA 130 litres capacity H Vitosilver part no 7171 641 160 litres capacity H Vitosilver part no 7171 640 H Vitowhite part no 7171 903 200 litres capacity H Vitosilver part no 7171 639 H Vitowhite part no 7171 904 5692 328 GB Subject to technical modifications Printed on environmentally friendly chlorine free bleache...

Reviews: