54
Setting parameters using "System scheme 7000"
as an example
To set a parameter, first select the parameter group
and then the parameter.
Service menu:
1.
Press and hold
OK
+
å
simultaneously for
approx. 4 s.
2.
Select
"Coding level 1"
.
3.
Select parameter group:
"System definition"
4.
Select parameter:
"System scheme 7000"
5.
Set a system scheme: e.g.
"6"
Alternatively, if the service menu was already active:
Extended menu:
1.
å
2. "Service"
3.
Select
"Coding level 1"
.
4.
Select parameter group:
"System definition"
5.
Select parameter:
"System scheme 7000"
6.
Set a system scheme: e.g.
"6"
Required parameters for components connected on site
Parameters may need to be set subject to the appli-
ance type, the selected system scheme and the acces-
sories used.
Overview of required parameters: See the following
chapter.
Detailed explanations of parameters
"Vitotronic 200" service instructions
System scheme
System schemes
Component
System scheme
0
1
2
3
4
5
6
7
8
9
10
11
Heating circuit
A1/HC1
—
X
X
—
—
X
X
—
—
X
X
—
M2/HC2
—
—
—
X
X
X
X
X
X
X
X
—
M3/HC3
—
—
—
—
—
—
—
X
X
X
X
—
DHW cylinder
X
—
X
—
X
—
X
—
X
—
X
—
Immersion heater
0
—
0
—
0
—
0
—
0
—
0
—
Heating water buffer cylin-
der
—
0
0
X
X
X
X
X
X
X
X
—
External heat generator
0
0
*1
0
*1
0
0
0
0
0
0
0
0
—
Instantaneous heating water
heater
0
0
0
0
0
0
0
0
0
0
0
0
Swimming pool
—
0
0
0
0
0
0
0
0
0
0
—
Solar thermal system
0
—
0
—
0
—
0
—
0
—
0
—
Cooling
A1/HC1
—
0
0
—
—
0
0
—
—
0
0
—
M2/HC2
—
—
—
0
0
0
0
0
0
0
0
—
M3/HC3
—
—
—
—
—
—
—
0
0
0
0
—
Separate cooling circuit SKK
0
0
0
0
0
0
0
0
0
0
0
—
*1
Only in conjunction with a heating water buffer cylinder.
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
6153640