11
Installation room requirements
!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
The installation room must be dry and free from
the risk of frost:
■
Ensure ambient temperatures between 0 and
35 °C.
■
Max. 70 % relative humidity (corresponds to
an absolute humidity of approx. 25 g water
vapour/kg dry air)
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
!
Please note
Overloading the floor can result in damage to
the building structure.
Observe the permissible floor load. Take the
total weight of the appliance into account.
Total weight
Type BWC
Weight in kg
Heat pump
Heat pump mod-
ule
301.C06
149
78
301.C12
154
83
301.C16
163
92
To prevent the transmission of structure-borne noise,
never site the appliance above ceilings with wooden
joists, e.g. in the attic.
Minimum room volume (to EN 378):
Type BWC
Refrigerant
charge in kg
Minimum room
volume in m
3
301.C06
2.00
4.9
301.C12
2.30
5.6
301.C16
3.25
7.4
Minimum clearances
400
1000
200
Fig. 2
Other minimum distances may apply in con-
nection with accessories, e.g. with hydraulic
connection sets and/or NC-Box.
Installation instructions for the relevant accesso-
ries
Observe engineering information.
Brine/water heat pump technical guide
Preparing for installation
Siting and transport requirements
(cont.)
6153640
Installation