58
!
Please note
After the value
"1"
has been set for
"Enable
instantaneous heating water heater 7900"
,
the prompt
"Secondary circuit filled?"
auto-
matically appears. If this prompt is responded to
with
"No"
, the instantaneous heating water
heater will not be enabled. Set
"Enable instan-
taneous heating water heater 7900"
to
"2"
.
Fill the secondary circuit. Confirm prompt
"Sec-
ondary circuit filled?"
with
"Yes"
.
Enable instantaneous heating water heater for DHW heating
Parameter
Setting
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
Parameters for external heat generators
Parameter
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
Enable external heat source for DHW heating
Parameter
Setting
"External heat source"
Ó
"Enable external heat source for DHW heating 7B0D"
"1"
Parameters for immersion heater
Parameters
Setting
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
"Enable booster heaters for DHW heating 6014"
"1"
Parameters for swimming pool water heating
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"Swimming pool 7008"
"1"
Parameters for ice store system
Parameter
Setting
"System definition"
Ó
"Select primary source 7030"
"1"
"External extension 7010"
"2"
Parameter
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"2"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
6153640