16
Fitting the hydraulic connection set
■
The pipes of the primary circuit/secondary circuit
connection set are located in the EPP box, which is
positioned on top of the appliance on delivery.
■
With the primary circuit/secondary circuit connection
set, the on-site hydraulic lines can be connected at
the
top
of the heat pump.
Note
The following connection versions are possible with
the hydraulic connection sets available as accessories:
■
Connection of the primary lines to the right or left
■
Connection of all hydraulic lines at the back
Note
We recommend fitting shut-off devices to the connec-
tion set on site. This will allow the primary and secon-
dary circuit to be shut off for maintenance work.
Fitting the primary/secondary circuit connection set (standard delivery)
B
C
D
A
2.
5x
1.
5x
+
E
Fig. 8
A
Primary circuit flow (heat pump brine inlet), con-
nection Cu 28 x 1.5 mm
B
Primary circuit return (heat pump brine outlet),
connection Cu 28 x 1.5 mm
C
Secondary circuit flow (DHW cylinder), connection
Cu 28 x 1.5 mm
D
Secondary circuit flow (heating circuits), connec-
tion Cu 28 x 1.5 mm
E
Secondary circuit return (heating circuits DHW cyl-
inder), connection Cu 28 x 1.5 mm
Installation sequence
Siting the heat pump
(cont.)
6153640
Installation