72
Connections
ECO 33 to 55 and 65
ECO 61 to 151
Flow
DN
32
40
R
1¼”
1½”
Return
DN
32
40
R
1¼”
1½”
Cold water inlet
*5
On-site
DN
15
15
R
½”
½”
Cold water outlet
On-site
R
¾”
¾”
Required equipment
Po
s.
Designation
1
Pyromat ECO
3
High limit safety cut-out
4
Motor, primary air damper
5
Motor, secondary air damper
6
Motor, secondary air damper 2
7
Flue gas temperature sensor Pt1000
8
Flue gas fan
9
Lambda probe
qP
Flow temperature sensor
Thermally activated safety valve TS, R ¾, individually tested, opening temper-
ature 95-100 °C (safety heat exchanger integrated into the boiler)
qW
Return temperature sensor
qE
Temperature indicator (thermometer)
qR
Pressure gauge
qT
Boiler circuit pump
qZ
Return temperature raising facility
qU
Air separator (recommended: absorption deaerator)
qI
Safety valve, max. setting pressure 3.0 bar, type-tested according to DIN
3440
Nominal diameter of valve, connection line and discharge pipe to DIN 4751 Part
2
qO
Additional heat source
wP
Heating circuit 1
wQ
Heating circuit 2
*5
fixed pipework in metal, 2.5 to 3.5 bar
Appendix
Installation schemes
(cont.)
5604 447 GB