18
Coding in the delivered condition
Possible change
Party mode time limit
F2:8
Party mode can be active
for up to 8 hours.
F2:0
No time limit for party mode
Party mode is deactivated
when changing the heating
program to "Heating".
F2:1
to
F2:12
Time limit for party mode
adjustable from 1 to 12
hours.
DHW
Coding
Coding in the delivered condition
Possible change
DHW differential
0C:0
Differential temperature
is calculated automati-
cally.
0C:1
to
0C:20
Fixed differential tempera-
ture adjustable between
1 ° C and 20° C.
DHW return temperature
0D:10
Flow control activated.
Set return temperature
corresponds to DHW
temperature plus 10 °C
0D:0
Flow control deactivated.
Valve is always fully
opened.
0D:1
to
0D:30
Flow control activated. Set
return temperature corre-
sponds to DHW tempera-
ture plus value set in °C.
Setting range between 1° C
and 30° C.
Code 2
The coding addresses are displayed in categories that are subject to the respective
system configuration:
■
"General"
Coding addresses "80" , "81", "90"
■
"Heating"
Coding addresses "A3" , "A4"
Codes
Code 1
(cont.)
5604 447 GB