59
1.
Determine the required annular gap from the dia-
grams, taking into account the calculated pressure
drop and air flow rate for the individual section.
Example:
Engineering plans provide the following details for
the individual section:
■
Supply air vent for ceiling installation: DN 125, air
discharge angle 360°
■
Pressure drop: 20 Pa
■
Air flow rate: 52 m
3
/h
Annular gap to be set: 6 mm
2.
Set determined annular gap
A
at the supply air
vent for ceiling installation.
3.
Record the value in the commissioning report.
Extract air vent
Part no. 7506394
A
a
Fig. 84
A
Vent cone setting in mm
■
Nominal diameter DN 125
■
Dimension a: 160 mm
■
Max. air flow rate 60 m
3
/h
Commissioning, inspection, maintenance
Presetting supply air and extract air apertures
(cont.)