25
In order to keep deviations in the air flow rate as low
as possible, install an iris diaphragm with defined mini-
mum clearances.
Minimum clearance
■
Before/after bend: 1 x D
■
Before tee: 3 x D
■
After tee: 1 x D
■
Before air outlet: 3 x D
Iris diaphragms: DN 125 and 160
Install the iris diaphragm in the ductwork between 2
floors.
Ø D
A
B
Fig. 21
C
A
B
Ø d
Fig. 22
A
Setting lever
B
Test connector
Dimensions of iris diaphragm
Iris diaphragm
DN
125
160
7
d
mm
124
159
C
mm
63
60
7
D
mm
210
230
A
Fig. 23
Installation of iris diaphragm
A
Ceiling / floor
Note
The iris diaphragm must be accessible for adjustment
and cleaning.
Installing supply air/extract air header
Installing the iris diaphragm
5831646
Installation