Specification and product characteristics (to EnEV [Germany])
Rated output
Full load
kW
72
84
96
108
120
132
144
Partial load
kW
46.8
54.6
62.4
70.2
78.0
85.8
93.6
Flue pipe
7
(inter-
nal diameter)
mm
180
200
225
225
250
250
250
Required draught
Pa
3
3
3
3
3
3
3
mbar
0.03
0.03
0.03
0.03
0.03
0.03
0.03
Flue gas
Temperature (gross)
Full load
°C
124
116
113
111
114
114
118
Partial load
°C
91
85
82
86
82
84
82
Mass flow rate
Full load
kg/h
170
186
226
262
278
306
320
Partial load
kg/h
149
165
195
233
244
268
277
Efficiency
η
&
100 % of rated
output
%
92.1
92.1
92.3
92.4
92.4
92.4
92.5
&
30 % of rated out-
put
%
93.0
93.5
93.4
93.3
93.5
93.4
93.4
Standby loss
q
B,70
%
1.0
0.9
0.9
0.9
0.8
0.8
0.8
Power consump-
tion
(standard
value) at
&
100 % of rated
output
W
351
377
402
426
448
469
489
&
30 % of rated out-
put
W
117
126
134
142
149
156
163
Chimney information
Observe the required draught when sizing the chimney.
Apply the flue gas values (measured downstream of the draught hood) as calcu-
lating values for sizing the chimney in accordance with DIN 4705 [or local regu-
lations].
The flue gas temperature is measured at 20 °C combustion air temperature.
Specification
33
Specification
5692
647
GB
Summary of Contents for GS1B
Page 29: ...Parts lists cont 29 Parts lists 5692 647 GB ...
Page 30: ...Parts lists cont 30 Parts lists 5692 647 GB ...
Page 31: ...Parts lists cont 31 Parts lists 5692 647 GB ...
Page 37: ...37 5692 647 GB ...
Page 38: ...38 5692 647 GB ...
Page 39: ...39 5692 647 GB ...