6.
&
Check the sensor position, if the
flue gas monitor shuts down the
burner later than after 2 minutes.
&
Replace the sensor or the burner
control unit, if any of the following
faults occur:
–
The flue gas monitor does not
switch off.
–
The burner will not start.
–
The sensor is corroded.
7.
Shut down your heating system.
8.
Remove the cover, and push the
flue pipe onto the draught hood.
9.
Start the boiler.
Instructing the system user
The system installer must hand the operating instructions to the system user
and instruct him/her in the operation of the system.