Checking the flue gas monitor
A
Sensor
1.
Shut down your boiler.
2.
Pull the flue pipe from the draught
hood.
3.
Cover the flue pipe adaptor on the
draught hood with a suitable object
to carry out the function test.
4.
Start the boiler.
5.
The flue gas monitor must shut
down the burner within 2 minutes.
The burner will then be locked out
for approx. 17 minutes.
Further details regarding the individual steps
(cont.)