12
A
B
Fig. 7
1.
Disconnect the power supply and safeguard
against unauthorised reconnection.
2.
Remove cap
A
, taking care with heating indicator
light
B
.
3.
Remove heating indicator light
B
from the cap for
safekeeping.
Resetting the high limit safety cut-out
The high limit safety cut-out switches the immersion
heater off at a sensor temperature of 100 °C.
A
B
B
Fig. 8
1.
Remove cap
A
(see page 12).
The resetting feature
B
is
red
when locked.
2.
Press resetting feature
B
with a screwdriver.
The resetting feature
B
turns
black
when
unlocked.
3.
Refit cap
A
along with the heating indicator light.
4.
Switch the power on again.
Note
If the high limit safety cut-out locks several times in a
row, the TR/HLSC (temperature controller/high limit
safety cut-out) combination device must be replaced.
Replacing the TR/HLSC combination device
A
C
B
B
D
Fig. 9
1.
Remove cap
A
2.
Disconnect cables
B
from TR/HLSC combination
device
C
.
3.
Remove 2 screws
D
from the retainer.
4.
Fit new TR/HLSC combination device
C
.
Commissioning, inspection, maintenance
Removing the cap from the immersion heater
5677415