73
Controller and sensor PCB
aVG
F23
F0
sVA
X31
X25
X15
X24
F26
F20
F21
F14
F16
F12
F13
F7
F8
F6
F4
F27
F11
20
1
J3
J4
X2
X3
X20
Fig. 35
F..
For connections, see the following table.
J3
Jumper for terminator Modbus 2
Terminator enabled
Terminator disabled
J4
Jumper for setting master/slave, Modbus 2
Heat pump controller is slave.
Heat pump control unit is master.
X2
Connection, power supply to main PCB
X3
Connection, connecting lead to main PCB
X15 Connecting cable to the heat pump: KM-BUS
X20 Programming unit connection
X24 Slot for LON communication module
X25 Connecting lead to the heat pump: Low voltage
< 42 V (sensors)
X31 Coding card slot
aVG
KM-BUS
sVA
Modbus 2 (wires
not
interchangeable):
Data connection to higher ranking control unit
Plug F0
Plug
Sensor
Type
F0.1/F0.2
Fixed value resistor
—
F0.2/F0.3
Radio clock receiver
DCF
Plug X25 (factory connection)
Plug
Sensor
Type
(X25.1/X25.2)
Flow temperature sensor, primary circuit
Pt500A
(PTC)
(X25.3/X25.4)
Return temperature sensor, primary circuit
Pt500A
(PTC)
(X25.9/X25.10)
Flow temperature sensor, secondary circuit
Pt500A
(PTC)
(X25.11/
X25.12)
Return temperature sensor, secondary circuit
Pt500A
(PTC)
Temperature sensor curves: See page 80.
Maintenance
Electrical connections on the heat pump control…
(cont.)
5800 917 GB
Maintenance