53
1. Service menu:
Press
OK
+
å
simultaneously and hold for
approx. 4 s.
2. "Coding level 1"
3. "Compressor"
4.
Select parameter.
5000 Enable compressor
Enabling of the compressor for operation of the heat
pump
Value
Meaning
"0"
Compressor is blocked.
"1"
Compressor is enabled.
5012 Enable use of compressor stage
Setting in the bit field (see chapter "Setting parame-
ters"): Several bits can be selected.
Note
opens the setting wizard.
!
Please note
The compressor will not start if
no
bit has been
selected.
■
Select at least
"Bit 2"
.
The setting value results from the combination of se-
lected bits.
5030 Output compressor stage
Type-dependent heating output of heat pump:
This value is required to calculate the energy state-
ment and seasonal performance factor, for example.
!
Please note
Incorrect setting leads to a flawed energy state-
ment.
For Vitocal 300-G, type BW 301.C17 set 17 kW.
Setting value in kW
5043 Primary source output
Never adjust
Parameter group Compressor
Calling up the parameter group