61
1098.5 "Calorific value"
Setting
Explanations
Value is provided on the gas supplier's bill.
Used for gas consumption data.
10.0000
5.0000 to
40.0000
Calorific value adjustable from 5.0000 to
40.0000 kWh/m
3
in increments of 0.0001
1139.0 "Outside temperature limit for cancelling reduced set room temperature"
Setting
Explanations
Temperature limit for cancelling reduced set room
temperature
-5
Temperature limit in the delivered condition - 5 °C
-61 to +10 Temperature limit adjustable from - 61 to + 10 °C in
1°C increments
1139.1 "Outside temperature limit for raising the reduced set room temperature to the standard set room
temperature"
Setting
Explanations
Temperature limit for raising the reduced set room
temperature (see function description)
-14
Temperature limit in the delivered condition - 14 °C
-60 to +10 Temperature limit adjustable from - 60 to + 10 °C in
1 °C increments
1504.0 "Source for date and time"
Setting
Explanations
Selection of source for date and time
The setting depends on the heat generator and acces-
sories.
Local
0
Factory setting: The date and time are adopted from
the control unit.
1
Internet protocol (see parameter "508.0")
Boiler
Note
Parameter values in
bold
are factory settings.
521.0 "Time interval in burner hours until the next service"
Setting
Explanations
Number of burner hours to run until next service
0
0 to 25500 Burner hours until next service adjustable from 0 to
25500
System configuration (parameters)
General
(cont.)
6151778
Parameter