Draining the boiler on the heating water side
A
Fig. 51
1.
Close the shut-off valves on the heating water side.
2.
Connect hose to air vent valve
A
and route it into
a suitable container or drain outlet.
3.
By means of an actuator test, move the 3-way
valve to its centre position.
4.
Open air vent valve
A
and drain the boiler as
much as required.