66
426.4 "Duration for set flow temperature increase, heating circuit 2"
Setting
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60 min
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
428.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 3"
Setting
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0 K
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
428.4 "Duration for set flow temperature increase, heating circuit 3"
Setting
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60 min
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
933.3 "Priority, DHW heating, heating circuit 1"
Setting
Explanations
Priority of DHW heating over the heating circuit
Note
If several heating circuits are connected, only adjust in
conjunction with low loss header.
Off
0
Without DHW heating priority
DHW
1
With DHW heating priority
933.6 "Operating mode of heating circuit 1"
Setting
Explanations
Only adjust for systems with one heating circuit.
Heating mode:
Weather-compensated without room tem-
perature hook-up
4
Weather-compensated
without
room temperature in-
fluence
Weather-compensated with room tempera-
ture hook-up
7
Weather-compensated
with
room temperature influ-
ence (see also parameter 933.7)
System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating…
(cont.)
6151778
Parameter