27
Tighten nuts with the following torque:
Type AWT-AC Line
Connection
to external
unit
Torque in Nm
221.A04
Liquid line
7
6 mm
⁷
⁄
₁₆
UNF
14–18
Hot gas line
7
12 mm
¾ UNF
50–62
221.A07
Liquid line
7
10 mm
⅝ UNF
33–42
Hot gas line
7
16 mm
⅞ UNF
63–77
221.A10
Liquid line
7
10 mm
⅝ UNF
33–42
Hot gas line
7
16 mm
⅞ UNF
63–77
221.A13
Liquid line
7
10 mm
⅝ UNF
33–42
Hot gas line
7
16 mm
⅞ UNF
63–77
221.B10
Liquid line
7
10 mm
⅝ UNF
33–42
Hot gas line
7
16 mm
⅞ UNF
63–77
221.B13
Liquid line
7
10 mm
⅝ UNF
33–42
Hot gas line
7
16 mm
⅞ UNF
63–77
Connection to the internal unit
Note
We recommend using the pipe bends
supplied for connecting the refrigerant
lines. Depending on the installation con-
ditions, it may also be possible to con-
nect the refrigerant lines directly without
bends.
Installation sequence
Connecting refrigerant lines
(cont.)
5782 201 GB
Installation