15
Total weight with filled DHW cylinder
Type AWT-AC
Weight in kg
221.A04
364
221.A07
364
221.A10
367
221.A13
367
221.B10
367
221.B13
367
Minimum room volume (to EN 378):
Type AWT-AC
Minimum room
volume in m
3
221.A04
2.7
221.A07
4.9
221.A10
6.1
221.A13
6.1
221.B10
6.1
221.B13
6.1
Minimum clearances
Note
If using the secondary circuit connection
set (accessories), maintain a wall clear-
ance of approx. 80 mm.
Minimum room height h
Installation
h in mm
■
Without
pre-assembly/
DHW connection set (ac-
cessories)
2000
■
With
pre-assembly/DHW
connection set (accesso-
ries)
2100
Observe engineering informa-
tion.
Vitocal technical guide
Handling
The cylinder module can be removed
during transport.
!
Please note
Avoid damaging the appliance
during handling.
Never
put weight on the top, front
or side panels of the appliance.
Installation sequence
Installing the internal unit
(cont.)
5782 201 GB
Installation