33
5680 011 -10
Viessmann AirflowPLUS AH2A Installation, Operating and Service
Setting Fan Speed
(continued)
Note:
Power to the Viessmann AirflowPLUS air handler must be turned off before changing switch settings.
The above values are approximations only, actual results may vary.
Note:
Factory switch set positions are shown in bold.
AH2A-354 Viessmann AirflowPLUS Air Handler
1/2 hp ECM - Air Flow Selectable Options
Set at dip switch S2.
Installation
Heat Fan Speed Switches 1 & 2
OFF
OFF
1300
ON
OFF
980
OFF
ON
675
ON
ON
760
Adjust Fan Speed Switches 3 & 4
OFF/OFF
ON/OFF
OFF/ON
OFF/OFF
ON/OFF
OFF/ON
Heating CFM
1300
1430
1140
980
1050
860
Cooling CFM
1640
1804
1440
1270
1400
1100
Heating CFM
760
830
660
760
830
660
Cooling CFM
980
1050
860
740
800
650
Cool Fan Speed Switches 5 & 6
OFF
OFF
1640
ON
OFF
1270
OFF
ON
980
ON
ON
740
Cool Fan Speed Profiles Switches 7 & 8
Pre Run
Time Min.
Motor %
Short Run
Time Min.
Motor %
Motor OFF
Time Min.
Motor %
OFF
OFF
5
82
2
88
2
75
ON
OFF
3
82
2
88
2
75
OFF
ON
2
82
-
-
4
75
ON
ON
-
-
-
-
4
75