Viessmann AirflowPLUS AH2A Installation, Operating and Service
5680 011 -10
32
Setting Fan Speed
AH2A-213 Viessmann AirflowPLUS Air Handler
1/3 hp ECM - air flow selectable options
Set at dip switch S2.
Installation
Heat Fan Speed Switches 1 & 2
OFF
OFF
1050
ON
OFF
825
OFF
ON
675
ON
ON
550
Adjust Fan Speed Switches 3 & 4
OFF/OFF
ON/OFF
OFF/ON
OFF/OFF
ON/OFF
OFF/ON
Heating CFM
1050
1155
924
825
910
726
Cooling CFM
1175
1290
1034
925
1010
814
Heating CFM
675
740
594
550
605
484
Cooling CFM
750
825
660
600
660
528
Cool Fan Speed Switches 5 & 6
OFF
OFF
1175
ON
OFF
925
OFF
ON
750
ON
ON
600
Cool Fan Speed Profiles Switches 7 & 8
Pre-Run
Time Min.
Motor %
Short Run
Time Min.
Motor %
Motor OFF
Time Min.
Motor %
OFF
OFF
5
82
2
88
2
75
ON
OFF
3
82
2
88
2
75
OFF
ON
2
82
-
-
4
75
ON
ON
-
-
-
-
4
75
Note:
Power to the Viessmann AirflowPLUS air handler must be turned off before changing switch settings.
The above values are approximations only, actual results may vary.
Note:
Factory switch set positions are shown in bold.