81
Coding in the delivered condition
Possible change
31:...
Set speed of the internal circula-
tion pump when operated as boiler
circuit pump in %, specified by the
boiler coding card
31:0
to
31:100
Set speed adjustable from 0 to
100 %
38:0
Status of burner control unit: Op-
erational (no fault)
38:≠0
Status of burner control unit: Fault
"DHW"
Select group
"DHW"
(see page 75).
Coding
Coding in the delivered condition
Possible change
56:0
Set DHW temperature adjustable
from 10 to 60 °C
56:1
Set DHW temperature adjustable
from 10 to above 60 °C
Note
Max. value subject to boiler coding
card.
Observe the maximum permissible
DHW temperature.
57:0
Do not adjust
58:0
Without auxiliary function for DHW
heating
58:10
to
58:60
Input of a 2nd set DHW tempera-
ture, adjustable from 10 to 60 °C
(observe coding addresses "56" and
"63" in this group)
5E:0
Do not adjust
5F:0
Do not adjust
65:...
Do not adjust (Information on the
type of diverter valve, specified by
the boiler coding card)
67:40
For solar DHW heating: Set DHW
temperature 40 °C. Above the se-
lected set temperature, DHW re-
heating suppression is active
(DHW heating by the boiler only if
solar energy is insufficient).
67:0
to
67:95
Set DHW temperature adjustable
from 0 to 95 °C (limited by boiler-
specific parameters)
Observe setting for coding address
"56".
6C:100
Set speed of internal circulation
pump for DHW heating 100 %
6C:0
to
6C:100
Set speed adjustable from 0 to
100 %
6F:...
Max. heating output for DHW heat-
ing in %, specified by boiler coding
card
6F:0
to
6F:100
Max. heating output for DHW heat-
ing adjustable from min. heating out-
put to 100 %
71:0
DHW circulation pump: "ON" ac-
cording to time program
71:1
"OFF" during DHW heating to set
value 1
71:2
"ON" during DHW heating to set val-
ue 1
72:0
DHW circulation pump: "ON" ac-
cording to time program
72:1
"OFF" during DHW heating to set
value 2
Code 2
"Boiler"
(cont.)
5773 238 GB
Codes