77
Coding in the delivered condition
Possible change
Set value setting: Coding address
"9b" in this group.
Internal circulation pump function:
Coding address "3F" in this group.
3b:3
Function of DE2 input: External
blocking.
Internal circulation pump function:
Coding address "3E" in this group.
3b:4
Function of DE2 input: External
blocking with fault message input
Internal circulation pump function:
Coding address 3E
3b:5
Function of DE2 input: Fault mes-
sage input
3b:6
Function of DE2 input: Brief opera-
tion, DHW circulation pump (keypad
function).
Setting, DHW circulation pump run-
time: Coding address 3d
3C:0
Function of DE3 input at EA1 ex-
tension:
No function
3C:1
Heating program changeover
3C:2
External demand with set flow tem-
perature.
Set value setting: Coding address
"9b" in this group.
Internal circulation pump function:
Coding address "3F" in this group.
3C:3
External blocking.
Internal circulation pump function:
Coding address "3E" in this group.
3C:4
External blocking with fault message
input
Internal circulation pump function:
Coding address "3E" in this group.
3C:5
Fault message input
3C:6
Brief operation, DHW circulation
pump (keypad function).
Setting, DHW circulation pump run-
time: Coding address "3d" in this
group
3d:5
DHW circulation pump runtime for
brief operation: 5 min
3d:1
to
3d:60
DHW circulation pump runtime ad-
justable from 1 to 60 min
3E:0
Internal circulation pump stays in
control mode at signal "External
blocking"
3E:1
Internal circulation pump stops at
signal "External blocking"
3E:2
Internal circulation pump starts at
signal "External blocking"
3F:0
Internal circulation pump stays in
control mode at signal "External
demand"
3F:1
Internal circulation pump stops at
signal "External demand"
3F:2
Internal circulation pump starts at
signal "External demand"
4b:0
Function of input
lH
: No function
4b:1
External demand
4b:2
External blocking
Code 2
"General"
(cont.)
5773 238 GB
Codes