Installation Instructions
28 of 38
IM-PP 724607 1218 ProPress
Tube
Diameter
(inches)
Minimum
Insertion
Depth (inches)
Minimum
Insertion
Depth (mm)
Maximum
Insertion
Depth (inches)
Maximum
Insertion
Depth (mm)
½
¾
19
⅞
22
¾
⅞
23
1⅛
28
1
⅞
23
1⅛
28
1¼
1
26
1
3
/
16
30
1½
1
7
/
16
37
1
9
/
16
40
2
1
9
/
16
40
1¾
44
Table 20: Insertion depths for ProPress non-stop couplings
Non-stop couplings and extended non-stop couplings are often used to
conduct repairs. Without a stop, these couplings can slide completely
onto a tube and allow a connection to be made in tighter spaces. Unlike
fittings with an integrated stop that have a minimum insertion depth,
non-stop couplings have minimum and maximum allowable insertion
depths. Both the minimum and the maximum insertion depths must be
marked and a line connecting the two marks. Drawing a line between the
minimum and maximum insertion marks distinguishes a good connection
on a non-stop fitting from a bad connection on a fitting with a stop.
Tube
Diameter
(inches)
Minimum
Insertion
Depth (inches)
Minimum
Insertion
Depth (mm)
Maximum
Insertion
Depth (inches)
Maximum
Insertion
Depth (mm)
½
¾
19
2¼
57
¾
⅞
23
2⅝
67
1
⅞
23
2⅞
73
1¼
1
26
3⅛
80
1½
1
7
/
16
37
3
5
/
16
84
2
1
9
/
16
40
3¾
95
Table 21: Insertion depths for ProPress extended non-stop couplings
▶
While turning slightly, slide press fitting onto the tube to the marked
insertion depth.
Note:
End of tube must contact stop.