IM-PP 724607 0815
9
1.5
Applications
Listed below are common applications approved by Viega for Viega ProPress fitting systems.
Table 1.1
Types of Service
System Operating Conditions
ProPress
304 Stainless
ProPress
316 Stainless
ProPress
ProPressG
MegaPress
MegaPressG
Comments
Pressure
Temperature
FKM
EPDM
EPDM
HNBR
EPDM
HNBR
Fluids/Water
Hot and Cold
Potable Water
200 PSI
32˚F-250˚F
√
√
Rainwater/
Gray Water
200 PSI
Note 3
√
√
√
Fire Sprinkler
175 PSI
Note 3
√
√
√
Chilled Water
Ethylene Glycol /
Propylene Glycol
200 PSI
Note 3
√
√
√
√
Hydronic Heating
Ethylene Glycol /
Propylene Glycol
200 PSI
Note 3
√
√
√
√
Cooling Water
Up to 50% Ethylene Glycol or
Propylene Glycol solution
200 PSI
Note 3
√
√
√
√
Deionized Water
200 PSI
158˚F
√
Low-Pressure
Steam
Up to 15
PSI
248˚F
√
√
√
√
Isopropyl Alcohol
200 PSI
75˚F
√
Latex Paint
200 PSI
32˚F-250˚F
√
Methyl Ethyl
Ketone
200 PSI
100˚F
√
Nitric Acid
10%
200 PSI
73˚F
√
√
Phosphoric Acid
25%
200 PSI
Ambient
√
Paraffin Wax
200 PSI
100˚F
√
Fuel, Oil and Lubricant
Heating
Fuel Oil
125 PSI
Note 3
√
√
√
Diesel Fuel
125 PSI
Note 3
√
√
√
Ethanol
Pure Grain Alcohol
200 PSI
Note 3
√
√
Propane
Compliant with CSA LC4
125 PSI
-40˚F-180˚F
√
√
Butane
Compliant with CSA LC4
125 PSI
-40˚F-180˚F
√
√
Kerosene
Note 3
68˚F
√
√
√
Lube Oil
Petroleum Based
200 PSI
Note 3
√
√
√
Gases
Compressed Air
Less than 25mg/m
3
oil content
200 PSI
Note 3
√
√
√
√
√
√
Compressed Air
More than 25mg/m
3
oil content
200 PSI
Note 3
√
√
√
Natural Gas
Compliant with CSA LC4
125 PSI
-40˚F-180˚F
√
√
Oxygen - O
2
(nonmedical)
Keep oil and fat free /
non-liquid O
2
140 PSI
Up to 140˚F
√
√
√
√
√
Nitrogen - N
2
200 PSI
Note 3
√
√
√
√
√
√
Carbon Dioxide
- CO
2
200 PSI
Note 3
√
√
√
√
Ammonia
Anhydrous
200 PSI
122˚F
√
Acetylene
200 PSI
86˚F
√
√
Argon
Welding Use
200 PSI
Ambient
√
√
√
√
√
Hydrogen - H
2
125 PSI
0˚F-250˚F
√
√
√
Vacuum
29.2 in Hg
Note 3
√
√
√
√
√
√
1. All systems are recommended to be clearly labeled with the fluid or gas being conveyed. For further information please consult Viega Technical Services.
2. All Viega systems must be used with the manufacturer’s recommended sealing element. Contact your local Viega representative or Viega Technical Services for application
temperature, pressure and concentration limits.
3.
System pressure and temperature ranges depend on sealing element.
Summary of Contents for Megapress