3. Installation 

 

3.1 Connection to the battery 

In order to utilize the full capacity of the product, batteries with sufficient capacity and 
battery cables with sufficient cross section should be used. See table: 
 
 

12/250 

24/250 

48/250 

Minimum battery capacity 

38 Ah 

22 Ah 

14 Ah 

Internal DC fuse 

60A 

30A 

25A 

Recommended DC cable 
cross-section (mm

2

 

 

 

– 1,5 m 

4 mm

²

 

2,5 mm

²

 

1,5 mm

²

 

1,5 

– 3 m 

6 mm

²

 

4 mm

²

 

2,5 mm

²

 

 
 

12/375 

24/375 

48/375 

Minimum battery capacity 

66 Ah 

38 Ah 

22 Ah 

Internal DC fuse 

80A 

40A 

25A 

Recommended DC cable 
cross-section (mm

2

 

 

 

– 1,5 m 

6 mm

²

 

4 mm

²

 

2,5 mm

²

 

1,5 -3 m 

10 mm

²

 

6 mm

²

 

4 mm

²

 

 
The inverters are fitted with an internal DC fuse (see table above for rating). If the DC 
cable length is increased to more than 1,5 m, an additional fuse or DC circuit breaker 
must be inserted close to the battery. 
 
Reverse polarity connection of the battery wires will blow the internal fuse and can 
damage the inverter. The internal fuse it not replacable. 
 

3.2 Connection to the load 

Never connect the output of the inverter to another AC source, such as a household 
AC wall outlet or a generator. 
 

3.3 Remote on/off connector 

A remote on/off switch can be connected to the two pole connecter. Alternatively, the 
left hand contact of the connector can be switched to battery positive: useful in 
automotive applications, wire it to the ignition contact. 
 
Note that also the front switch needs to set to either On or ECO for the inverter to 
start. 

 
3.4 Configuration 

The inverter is ready for use with the factory settings (see specifications), and can be 
configured with a computer (VE.Direct to USB interface cable needed), Apple and 
Android smartphones, tablets and other devices (VE.Direct to Buetooth Low Energy 
(BLE) dongle needed). 

Summary of Contents for Phoenix 12/250

Page 1: ...Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 24 250 24 375 48 250 48 375...

Page 2: ......

Page 3: ...assis must be grounded A grounding point is located on the outside of the product Whenever it is likely that the grounding protection has been damaged the product must be turned off and secured agains...

Page 4: ...reliability over many years The inverters are short circuit proof and protected against overheating whether due to overload or high ambient temperature High start up power Needed to start loads such a...

Page 5: ...C circuit breaker must be inserted close to the battery Reverse polarity connection of the battery wires will blow the internal fuse and can damage the inverter The internal fuse it not replacable 3 2...

Page 6: ...LED indicates the reason for shutdown Remove the cause and then restart the inverter by switching it Off and then back On Red LED Definition Trouble shooting Solid on Overload Reduce load Slow blink L...

Page 7: ...it Off and then On or recharge the battery as soon as the battery has risen and then stayed above the Charge detect level for 30 seconds it will switch on See the Technical Data table for default low...

Page 8: ...2 a f Operating temperature range 40 to 60 C fan assisted cooling derate 3 per C above 40 C Humidity non condensing max 95 ENCLOSURE Material Colour Steel chassis and plastic cover blue Ral 5012 Batt...

Page 9: ...EN NL FR DE ES Appendix the Digital Multi Control Fig 1 Front and rear view FigFi...

Page 10: ...00 Date 20 January 2016 Victron Energy B V De Paal 35 1351 JG Almere PO Box 50016 1305 AA Almere The Netherlands General phone 31 0 36 535 97 00 Customer support desk 31 0 36 535 97 03 Fax 31 0 36 535...

Reviews: