background image

Check ambient temperature and check if the two built-in fans are running. Reduce the ambient temperature.

Settings invalid

Settings data is corrupt. Reset to factory defaults.

8.4. BMS issues

8.4.1. The BMS frequently disables the battery charger

A well-balanced battery does not disable the charger, even when the batteries are fully charged. But when the BMS frequently
disables the charger, this is an indication of cell imbalance.

In case of moderate or large cell imbalance it is an expected behaviour that the BMS frequently disables the battery charger. This
is the mechanism behind this behaviour:

As soon as one cell reaches 3.75V, the BMS disables the charger due to high cell voltage. Whilst the charger is disabled, the
cell balancing process still continues, moving energy from the highest cell into adjacent cells. The highest cell voltage drops and
as soon as it falls below 3.6V, the charger is activated again. This cycling typically takes between one and three minutes. The
voltage of the highest cell will rise again quickly (this can be in a matter of seconds), after which the charger will be disabled
again and so forth. This does not indicate a problem with the battery or the cells and will continue with this behaviour until all cells
are fully charged and balanced. This process might take several hours, depending on the level of imbalance. In case of serious
imbalance this process can take up to 12 hours. Balancing will continue throughout this process and balancing even takes place
when the charger is disabled. The continued enabling and disabling of the charger can appear strange, but rest assured that
there is no problem. The BMS is merely protecting the cells from over voltage.

8.4.2. The BMS is prematurely turning loads off

This could be because of a cell imbalance.

If a cell voltage falls below the "Allowed-to-Discharge cell voltage" setting in the battery (default 2.8V), the BMS will turn the loads
off.

Check the cell voltages of all batteries that are connected to the BMS using the VictronConnect app. Also check if all batteries
have the same "Allowed-to-Discharge cell voltage" settings.

Once the loads have been turned off due to low cell voltage, the cell voltage of all cells needs to be 3.2V or higher before the
BMS will turn the loads back on.

8.4.3. The pre-alarm setting is missing in VictronConnect

Pre-alarm is only available if the battery supports it. The current battery models all support it, but older batteries do not have the
hardware required for the pre-alarm feature.

8.4.4. BMS is displaying alarm while all cell voltages are within range

A possible cause is a loose or damaged BMS cable or connector. Check all BMS cables and their connections.

Also consider that once there has been a cell under voltage alarm, the cell voltage of all cells need to be increased to 3.2V before
the battery clears the under voltage alarm.

A way to rule out if a fault is originating from a faulty BMS or from a faulty battery is to check the BMS using one of the following
BMS test procedures:

Single battery and BMS check:

• Disconnect both BMS cables from the BMS.

• Connect a single BMS extension cable between both BMS cable connectors. The BMS cable should be connected in a loop, as

in below diagram. The loop tricks the BMS in thinking that there is a battery connected without any alarms.

• If the alarm is still active after the loop has been placed, the BMS is faulty.

• If the BMS cleared the alarm after the loop has been placed, the battery is faulty and not the BMS.

Lynx Smart BMS

Page 25

Troubleshooting and Support

Summary of Contents for Lynx Smart BMS 500

Page 1: ...Lynx Smart BMS ENGLISH ...

Page 2: ... ATC controlled loads and chargers 9 5 3 6 Wiring a Remote on off switch 10 5 3 7 Programmable relay wiring 10 5 3 8 Connect the GX device 11 5 4 System examples in detail 11 5 4 1 Lynx Smart BMS 2x Lynx Distributor and lithium batteries 11 5 4 2 Lynx Smart BMS 1x Lynx Distributor and lithium batteries 12 5 4 3 Lynx Smart BMS only 13 6 Configuration and settings 14 6 1 Power up for the first time ...

Page 3: ...ncomplete current reading 27 8 5 2 Incorrect state of charge reading 27 8 5 3 State of charge does not increase decrease fast enough or too fast when charging discharging 27 8 5 4 Synchronisation issues 27 8 6 VictronConnect issues 28 8 7 GX device issues 28 9 Warranty 29 10 Technical specifications 30 11 Appendix 31 11 1 LED indications warnings alarm and error codes 31 11 2 Supported NMEA 2000 P...

Page 4: ...ck safety mechanism and also suitable as a remote controllable main system switch Battery monitor indicating state of charge percentage and more data Pre alarm signal provide a warning before the system shuts down due to a low cell voltage Bluetooth for use with our VictronConnect App for setup monitoring and diagnostic Local and remote monitoring using a Victron GX device for example the Cerbo GX...

Page 5: ...ttery in case the primary controls ATC and ATD contacts as well as DVCC fail to disable the loads and or chargers when required 2 It can be used as a remote controlled main system on off switch via the VictronConnect app a GX device only Standby and On as well as using the Remote on off terminals 2 3 Built in pre charge circuit The built in pre charge circuit pre charges capacitive loads such as i...

Page 6: ...ional state battery SoC and alarms and make them available to be controlled via our remote monitoring VRM portal Lynx Distributor fuse monitoring via our VictronConnect app and a connected GX device Communication with the Lynx Distributors is via it s RJ10 connectors The Lynx Smart BMS can be used to read out the Lynx Distributors generate alarms in case a fuse is blown or communication is lost Fu...

Page 7: ... the front of the units is upside down as well use the special stickers are included with each Lynx module so that the text is orientated the correct way Fused battery connections Fused DC loads and charge connections Battery monitor BMS and contactor Lynx Smart BMS with two Lynx Distributors From battery bank To DC system All DC loads and DC charge sources Example of Lynx module orientation the b...

Page 8: ...A 6kW 12kW 24kW 4 2 2 Fusing The Lynx Smart BMS is not a system fuse It only warns when the current is too high Fusing needs to be done externally for example by connecting Lynx Distributor modules to the Lynx Smart BMS or by using external fuse holders and fuses Always use fuses with the correct voltage and current rating Match the fuse rating to the maximum voltages and currents that potentially...

Page 9: ...rk on batteries should be carried out by qualified personnel only Observe the battery safety warnings as listed in the battery manual Store this product in a dry environment The storage temperature should be 40 C to 65 C No liability can be accepted for damage in transit if the equipment is not transported in its original packaging 5 2 Mechanical connections 5 2 1 Lynx Smart BMS connection feature...

Page 10: ...is the DC system side Connect all Lynx modules to each other using the M8 holes and bolts on the left and right Take care that the modules correctly slot into the rubber joiner recesses Place the washer spring washer and nut on the bolts in the correct order and tighten the bolts to a torque of 14Nm Mount the Lynx assembly in its final location using the 5mm mounting holes Lynx module M8 bolt M8 S...

Page 11: ...r with the retainer clip of the RJ10 connector facing away from you Feed the RJ10 cable through the recess at the bottom of the Lynx Distributor see above picture Plug the RJ10 cable into the RJ10 connector at the bottom of the Lynx Smart BMS Connection example Lynx Smart BMS system RJ10 cables indicated in yellow 5 3 3 Connect BMS cables Connect the BMS cables from the lithium battery to the BMS ...

Page 12: ...s A common example is by providing 12V wired from AUX equal to system voltage to pin 3 and pin 5 An active high signal is then delivered to the connected remote H ports of the chargers and loads via pin 4 respectively pin 6 In case of a low cell voltage ATD opens the contact between pin 5 and pin 6 The load is then switched off and further discharge is prevented If the temperature is too low to ch...

Page 13: ...in 11 For the Lynx Smart BMS to operate the contact between pin 10 and pin 11 must be closed 5 3 7 Programmable relay wiring The programmable relay is an SPDT relay Single Pole Double Throw with 3 contacts Common COM Normally Open NO Normally Closed NC The relay makes contact between COM and NC when the relay is not active while COM and NO makes contact when the relay is activated Depending on the...

Page 14: ...and a CCGX 5 4 System examples in detail 5 4 1 Lynx Smart BMS 2x Lynx Distributor and lithium batteries A Lynx Smart BMS with two Lynx distributors and a Cerbo GX with GX touch panel form the heart of this system They continuously monitor the batteries fuses connected loads chargers and inverter charger s A typical system can contain the following components Lynx Smart BMS with built in contactor ...

Page 15: ...as before but this time with a single Lynx Distributor on the load side of the Lynx Smart BMS and the lithium battery connected directly to the input of the Lynx Smart BMS This is useful if only a single lithium battery or a single series string of lithium batteries is used Otherwise the same components are used DC loads Solar charger Cerbo GX VE Bus VE Direct VE Can RJ10 cable BMS cables Lynx Sma...

Page 16: ...ther with a simple DC system Please also note that no GX device is used It is not absolutely necessary for the operation of the Lynx Smart BMS However without GX device it is not possible to control compatible inverter chargers and MPPTs via DVCC DC loads BMS cables ATD allowed to discharge Lynx Smart BMS Fuse System with a Lynx Smart BMS without other Lynx modules and GX device Lynx Smart BMS Pag...

Page 17: ...rmware press the UPDATE button The firmware update is even easier via the VRM Remote firmware update feature requires a GX device in the system and internet connection In case of a new installation it is also recommended to check and update the firmware of each connected lithium battery This is done via Bluetooth using the VictronConnect app in a similar manner to that outlined above Updating the ...

Page 18: ...x Smart BMS starts a new full charging cycle This can be adjusted if required A new charge cycle means that the CVL charge voltage limit is increased from 13 5V for a 12V battery to 14 2V In addition to the SoC threshold a new charging cycle is started after a firmware update when the battery voltages are below 12V 24V 48V 3V per cell or when a low cell voltage is detected Battery monitor settings...

Page 19: ...rge manually set the current state of charge Synchronise SoC to 100 manually synchronise SoC to 100 requires VictronConnect v5 70 or later and Venus OS v2 90 or later VictronConnect settings Lynx Smart BMS 6 4 Lynx Distributor settings These instructions only apply if the system contains one or more Lynx Distributors Each Lynx distributor must be addressed and set to A B C or D This is done via a ...

Page 20: ...Lynx Smart BMS Page 17 Configuration and settings ...

Page 21: ...city and the number of paralleled batteries is set correctly Check that the system voltage has been set correctly Check if the fuse names of the Lynx Distributor if applicable are correctly named If a GX device is connected check that it is powered from the Lynx Smart BMS AUX terminals Check that the Lynx Smart BMS displays correctly on the GX device Disconnect a random BMS cable and verify that t...

Page 22: ...Status LED Bluetooth LED Lynx Smart BMS LEDs Lynx Smart BMS Page 19 Commissioning and Operation of the Lynx Smart BMS ...

Page 23: ... time Standby The Lynx Smart BMS can be put into Standby mode via the soft switch in the VictronConnect app or via the GX device and is used when the boat is docked or the RV is parked to prevent accidental discharging and charging from sources on the system side All systems will be shut down except for equipment powered by the AUX power port from which we recommend for powering the GX device This...

Page 24: ...he low temperature threshold adjustable in battery has been reached the ATC contact opens and will turn off all chargers If the Lynx Smart BMS is connected to a GX device DVCC compatible chargers that are connected to the same GX device will be turned off as well 7 5 Battery monitor operation The Lynx Smart BMS has a built in battery monitor It measures battery voltage and current Based on these m...

Page 25: ...t v5 70 or later and Venus OS v2 90 or later 7 8 VictronConnect Bluetooth live data advertisement support Battery voltage current state of charge and remaining running time at a glance See what you want to know in seconds in the VictronConnect app Device list The advantage is that the data is available much faster together with data from other Bluetooth smart devices and the range exceeds that of ...

Page 26: ...ug the 11 pin multi connector from its socket and reinsert it after 5 seconds The BMS will activate and close its contactor so that the battery is again connected to the system even though the battery voltage might be too low The BMS will close the ATC and ATD contacts providing that the battery allows this However in case of an empty battery the ATD contact will stay open and only the ATC contact...

Page 27: ...rn off or remove some loads or chargers and rule out wiring problems or shorts Internal error Contact your Victron supplier if one of the following errors are occurring Internal supply error Red LED flashing 12 times every 4 seconds Initialization error Red LED flashing 9 times every 4 seconds Contactor failure Red LED flashing 10 times every 4 seconds Hardware error GX device alarm calibration lo...

Page 28: ... the cells from over voltage 8 4 2 The BMS is prematurely turning loads off This could be because of a cell imbalance If a cell voltage falls below the Allowed to Discharge cell voltage setting in the battery default 2 8V the BMS will turn the loads off Check the cell voltages of all batteries that are connected to the BMS using the VictronConnect app Also check if all batteries have the same Allo...

Page 29: ...f the BMS is functional To test if the BMS is functional disconnect one of the battery BMS cables and see if the BMS will go into alarm mode BMS Check BMS functionality by deliberately loosening a BMS cable 8 4 6 System in OFF mode This is indicated by the status LED off and the Bluetooth LED flashing every 3 seconds The Lynx Smart BMS goes into OFF mode once a low cell voltage event occurred and ...

Page 30: ...oltage Voltage Tail current of battery capacity Charge detection time minutes Practical example default battery monitor settings and a 12 8V 200Ah lithium battery for the conditions that must be met before synchronisation takes place The battery voltage has to be above 14 0V The charge current has to be less than 0 04 x battery capacity Ah For a 200Ah battery this is 0 04 x 200 8A Both above condi...

Page 31: ...and check if it is set to VE Can Lynx Ion BMS 250kbit s Also make sure that the Lynx Smart BMS is connected to the VE Can port of your GX device and not the BMS Can port e g on a Cerbo GX RJ45 terminator or cable issue VE Can devices connect in daisy chain to each other and a RJ45 terminator needs to be used with the first and last device in the chain When connecting VE Can devices always use manu...

Page 32: ...proper or unreasonable use or misuse neglect exposure to excess moisture fire improper packing lightning power surges or other acts of nature This limited warranty does not cover damage deterioration or malfunction resulting from repairs attempted by anyone unauthorized by Victron Energy to make such repairs Non compliance with the instructions in this manual will render the warranty void Victron ...

Page 33: ...harge port maximum current rating 0 5A at 60Vdc protected by resettable fuse Allow to discharge port maximum current rating 0 5A at 60Vdc protected by resettable fuse Programmable relay SPDT maximum current rating 2A at 60Vdc Connections Busbar M8 VE Can RJ45 and RJ45 terminator I O Screw terminals Battery BMS cables Male and female circular 3 pole connector with M8 screw ring Up to 26 batteries c...

Page 34: ...rnating System in bootloader mode updating firmware Red flashing 1 time every 4 seconds Warning see VictronConnect for more information Red flashing 2 times every 4 seconds Battery communication error check battery BMS cables Red flashing 3 times every 4 seconds High low cell voltage or high low temperature detected Red flashing 4 times every 4 seconds High BMS temperature detected Red flashing 5 ...

Page 35: ...ature If the fans are not running contact your Victron dealer W B04 112 Warning bad contactor Reduce the current to prevent an imminent system shutdown Do this by reducing the load or by turning loads off Contact your Victron dealer W B06 Load will disconnect The loads will be turned off in 30 seconds if fault is not resolved For example low battery voltage This warning is always in combined the r...

Page 36: ... battery settings in the VictronConnect app This error occurs when the battery voltage is outside all system voltage ranges 9V Vbat 60V E B11 11 Hardware error Contact your Victron dealer E B25 25 Pre charge error The load resistance is too low to pre charge the loads Disconnect or reduce some DC loads E B26 26 Contactor error Contact your Victron dealer E B34 34 Wrong system voltage Check battery...

Page 37: ...1 Class and function N2K device class Electrical generation N2K device function Battery For more information see the NMEA2000 MFD integration guide 11 3 List of battery monitor settings Description default value adjustable fixed automatic Battery capacity 200Ah Yes No No Charged voltage 14 0V 28 0V 56 0V Yes No No Tail current 4 Yes No No Zero current calibration No No Yes at power up Peukert expo...

Page 38: ...ogrammable relay COM Potential free contact 9 Programmable relay NO Potential free contact 10 Remote on off H Pull up resistor To remotely turn the Lynx Smart BMS on or off For full functionality see chapter Wiring a Remote on off switch 10 11 Remote on off L Pull down resistor 11 5 Lynx Smart BMS related menu structure of the GX device This is an overview of the Lynx Smart BMS related menu struct...

Page 39: ...istory reset Clear history Press to clear Clears all history data Diagsnostics Diagnostics Shows last known errors Fuses Distributor A Ok Possible states Ok Fuse blown Fuse 1 4 Ok Possible states Ok Not used Blown Distributor B Ok Possible states Ok Fuse blown Fuses 1 4 Ok Possible states Ok Not used Blown IO System switch Enabled Status of the system switch Allow to charge Yes Status of the ATC s...

Page 40: ...1 10 5 8 8 166 2 5 4 80 9 28 9 8 0 184 7 Rev02 Dimensions in mm LYN034160200 Lynx Smart BMS 500 Dimension Drawing Lynx Smart BMS D E F C 1 2 3 4 B A 3 2 1 5 C D 4 6 7 8 A B 8 7 6 5 F E Lynx Smart BMS enclosure dimensions Lynx Smart BMS Page 37 Appendix ...

Reviews: