5.3.8. Connect the GX device
Connect the Lynx Smart BMS VE.Can port to the GX device VE.Can port using a RJ45 cable.
Multiple VE.Can devices can be daisy chained, but make sure that the first and the last VE.Can device both have a VE.Can RJ45
terminator installed.
Power the GX device from the AUX + and AUX – terminal of the Lynx Smart BMS.
RJ45 VE.can
connectors
Location of the VE.Can connectors on the Lynx Smart BMS
VE.Can RJ45
terminator
VE.Can RJ45
terminator
RJ45 UTP
cable
GX device
power cables
Wiring example Lynx Smart BMS and a CCGX
5.4. System examples in detail
5.4.1. Lynx Smart BMS, 2x Lynx Distributor and lithium batteries
A Lynx Smart BMS with two Lynx distributors and a Cerbo GX with GX touch panel form the heart of this system. They
continuously monitor the batteries, fuses, connected loads, chargers and inverter/charger(s).
A typical system can contain the following components:
• Lynx Smart BMS with built-in contactor and battery monitor.
• Lynx Distributor with 2 fused paralleled lithium batteries and identical cable lengths for each battery (up to 5 paralleled series
strings can be used per system).
• Lynx Distributor with fused connections for chargers, inverter/charger(s) and loads.
• A Cerbo GX (or other GX device).
Lynx Smart BMS
Page 11
Installation