26
Battery Voltage Parameters (temperature at 25
℃
)
Table 7-4
Charging Parameters
Battery charging setting
Gel
AGM
Flooded
Over Voltage Disconnect Voltage
16V; x2/24V
16V; x2/24V
16V; x2/24V
Charging Limit Voltage
15.5V;x2/24V
15.5V;x2/24V
15.5V;x2/24V
Equalize Charging Voltage
-----
14.6V;x2/24V
14.8V;x2/24V
Boost/absorption Charging Voltage
14.2V;x2/24V
14.4V;x2/24V
14.6V;x2/24V
Float Charging Voltage
13.8V;x2/24V
13.8V;x2/24V
13.8V;x2/24V
Boost Reconnect Charging Voltage
13.2V;x2/24V
13.2V;x2/24V
13.2V;x2/24V
Low Voltage Reconnect Voltage
12.6V;x2/24V
12.6V;x2/24V
12.6V;x2/24V
Under voltage warning reconnect voltage
12.2V;x2/24V
12.2V;x2/24V
12.2V;x2/24V
Under Voltage Warning Voltage
12V; x2/24V
12V; x2/24V
12V; x2/24V
Low Voltage Disconnect Voltage
11.1V;x2/24V
11.1V;x2/24V
11.1V;x2/24V
Discharging Limit Voltage
10.8V;x2/24V
10.8V;x2/24V
10.8V;x2/24V
Equalize duration
-----
2 hours
2 hours
Boost duration
2 hours
2 hours
2 hours