12.2018
INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 / VITTORIA 10
13
From this menu, the default language can be set. – Bulgarian,
English, Netherlands, Deutsch.
10.2.5. Service technician settings.
Types of settings for service technician (entered with
service technician password)
Parameter
Factory settings
room fan
Temperature On
Determinate temperature when the room fan
switches on.
100
0
C
Hysteresis
Temperature difference between starting and
stopping of the room fan.
3
0
C
Initial cleaning
In Start mode
60 sec.
Pressure Level (test mode)
Checkup if the pressure switch will “close”
correctly during minimal blowing from the
smoke fan in start mode.
50%
Extinguishing
Sets the working duration of the smoke fan at
100% in cleaning mode. This mode is activated
when the stoves goes to stopping and
extinguishing mode.
100 sec.
Period
Determinates how often the cleaning procedure
has to be triggered. The set value is summed up
from the feed screw working time. By this way
it’s possible to set the cleaning based on the
calculation of the amount of the used pellets
600 sec.
Time / Mod 1 ; Mod 2 ; Mod 3
Determinates how long the intermediate
cleaning should last in the respective
modulation 1, 2, 3.
4÷198 sec.
Fan %
Determinates the power of the smoke fan in %
during intermediate cleaning.
1%÷ 99%
Restore all factory settings!
Only in ready mode
Ignition ½-we can choose between 1 and 2.Choosing 1 and then safe,
the ignition or OUT1 is off. Choosing 2 and then safe the ignition or
OUT1 is on.
Ignition ½ -we can choose between 1 and 2. Choosing 1 and then safe,
the ignition or OUT2 is off. Choosing 2 and then safe the ignition or
OUT2 is on.
Screw ½- we can choose between 1 and 2. Choosing 1 and then safe
the screw or OUT5 is off. Choosing 2 and then SAFE the screw or OUT5
is on.
Smoke fan- we can choose between 1%to 100%.Choosing from 1 to 100
and then safe, at the exit of the smoke fan or OUT4 is triggered
modulation of the power.