7
I-800
One-Step Solvent Cement
Victaulic Style #899 FireLock CPVC One-Step Solvent Cement must be
stored out of direct sunlight in an ambient temperature between 40°F and
110°F. The solvent cement may be used for a period of two years from the
date stamped on the container. Expired solvent cement must be dis-
carded in an environmentally friendly fashion, in accordance with local
regulations. To prolong the life of the cement, the containers must be kept
tightly closed when not in use and covered as much as possible during
use. Refer to the “Solvent Cementing Procedures” section, starting on
page 23, for more information.
SYSTEM APPROVALS, LISTINGS, USAGE,
AND STANDARDS
Victaulic FireLock CPVC Sprinkler System Products are Underwriters
Laboratories Inc. (UL) Listed and Factory Mutual (FM) Approved for use
in wet-pipe sprinkler systems. In addition, these products are approved
by NSF
®
International for use in potable water systems (refer to page 19
for more information). Victaulic Style #899 FireLock CPVC One-Step Sol-
vent Cement meets ASTM-F493 and NSF International requirements.
National Fire Protection Association (NFPA) Standards 13, 13R, and 13D
must be referenced for design and installation requirements in addition to
this manual.
The following section summarizes the agency approvals, listings, usage,
and standards that Victaulic FireLock CPVC Sprinkler System Products
meet. For more specific listing information concerning FM or NSF Interna-
tional, contact Victaulic.
Light Hazard Occupancies:
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use
in Light Hazard Occupancies, as defined in NFPA 13, “Standard for the
Installation of Sprinkler Systems.”
DANGER
• Before using Victaulic Style #899 FireLock CPVC One-Step Solvent Cement, refer to
ASTM-F402-93, “Standard Practice for Safe Handling of Solvent Cements, Primers,
and Cleaners Used for Joining Thermoplastic Pipe and Fittings.” In addition, refer to
the solvent cement Material Safety Data Sheet (MSDS) and the solvent cement can
label for important information.
• Victaulic Style #899 FireLock One-Step Solvent Cement is highly flammable. Make
sure all ignition sources are eliminated before use.
• Avoid breathing solvent cement vapors, and use solvent cement only in well-
ventilated areas. Explosion-proof, general mechanical ventilation or local exhaust is
recommended to maintain vapor concentrations below recommended exposure
limits. In confined or partially enclosed areas, a NIOSH-approved, organic-vapor
cartridge respirator with a full-face piece is recommended.
• Avoid frequent contact with skin. PVA coated gloves and an impervious apron are
recommended.
• Avoid contact with eyes. Splash-proof chemical goggles are recommended.
Failure to follow these instructions could result in serious personal injury.