I-800
Garage Installations:
Victaulic FireLock CPVC Sprinkler System Products are suitable for use in
garages requiring sprinklers, as defined in NFPA 13R, with the following
requirements:
1.
Minimum protection consisting of either one layer of
3
/
8
-inch thick
gypsum or
1
/
2
-inch thick plywood must be provided.
2.
Listed pendent or sidewall sprinklers with a maximum temperature
rating of 225°F must be used.
3.
All sprinklers must be installed per the manufacturer’s published
installation instructions.
4.
The system must be installed per the requirements of NFPA 13R
and these installation instructions.
High Temperature Areas:
• Victaulic FireLock CPVC Sprinkler System Products are suitable for use
in areas where ambient temperatures are within the range of 35° F to
150° F.
• Victaulic FireLock CPVC Sprinkler System Products can be installed in
areas, such as an attic, where the ambient temperature exceeds 150° F
if ventilation is provided or if insulation is used around the product to
maintain a cooler environment.
WARNING
• DO NOT install Victaulic FireLock CPVC Sprinkler System Products in an area where
the ambient temperature will exceed 150° F, unless ventilation is provided or
insulation is used around the product.
Failure to follow this instruction could result in significant property damage and
product damage.