background image

 

10

 

 

Get From

 

Terminal Equipment Controller 
Get From another device 
configuration utility 
Default value = 

Range is: 

0 to 254

 

Conditional parameter to Wireless models VTR73xxX5x00W 
 

Entering a MAC address enables an automatic routine that automatically fetches 
all the required configuration property of the current device from another one 
already configured to the same required property values.  

If another value than the default value of 255 is entered, user will then be prompted 
to exit the Configuration Menu thus leaving all other parameter configuration to be 
copied from the referenced controller MAC address. 

 

Ex.: If you are currently configuring MAC12 and that the settings 

match exactly

 

the settings of ZN MAC5, then enter 5 as the current parameter value. 

  If the process is successful and all required configuration properties have been 

copied, the value will revert back to 255 

  If the process is 

NOT

 successful and all required configuration properties have 

NOT been copied ( either the reference device is 

NOT

 the same model number 

or is offline or does not exists ) the value will revert back to 254 to indicate the 
failure of the process 

Leaving the Get From parameter to 255 means that every configuration 
parameters will be set manually.

 

BI 1 

Binary input no.1 configuration 

Default value = 

None

 

(None):

 No function will be associated with the input. Input can be used for remote 

network monitoring. 

 

(Rem NSB):

 remote NSB timer clock input. The scheduling will now be set as per 

the binary input. It provides low cost setback operation via a dry contact

 

 

Contact opened = Occupied 

 

Contact closed = Unoccupied 

 

(Motion NO) or (Motion NC):

 Advanced PIR occupancy functions using a 

Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor. 
Occupancy mode is now set as per applied PIR function and configuration. 
Application information and examples are available on document: 

APP-PIR-Guide-

Exx. 

This document will provide the installers and system designers with detailed 

examples on applications, parameter configuration information, sequence of 
operation, troubleshooting and diagnostic help required for the proper usage of the 
PIR accessory covers

  

 

(Window) 

EMS: Forces the system to disable any current heating or cooling action 

by the Terminal Equipment Controller. The mode stays the same and the current 
setpoints are the same Occupied setpoints. Only the outputs are disabled. There is 
a Door/Window alarm displayed on the Terminal Equipment Controller to indicate 
to the local tenant that the door/window needs to be closed for cooling or heating to 
resume. 

 

Contact opened = Window Opened 

 

Contact closed = Window Closed 

BI 2 

Binary input no.2 configuration 
Default value = 

None

 

(None)

: No function will be associated with the input. Input can be used for remote 

network monitoring. 
 

(Door Dry) Door contact & Motion detector:

 This configuration is only functional 

if binary input #1 is set to 

Motion NO 

or 

Motion NC 

or a 

PIR accessory cover

 is 

used. 

With this sequence enabled, the occupancy is now dictated through those 2 inputs. 
Any motion detected will set the zone to occupied status. The zone will remain 
permanently in occupied mode until the door contact switch opens momentarily. 
The Terminal Equipment Controller will then go in stand-by mode. If more 
movements are detected, the occupied mode will resume. While the door is 
opened, any movements detected by the remote PIR sensor or the PIR accessory 
cover will be ignored. Use a Normally Closed contact switching device. 

 

Contact opened = Door opened 

 

Contact closed = Door closed 

Summary of Contents for VTR73 Series

Page 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Page 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Page 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Page 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Page 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Page 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Page 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Page 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Page 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Page 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Page 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Page 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Page 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Page 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Page 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Page 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Reviews: