13

 

DHumiLCK

 

Dehumidification lockout 
 
Default value: 

On = Authorized

 

Conditional parameter to Humidity models VTR735xX5x00(X)

 

Typically toggled through the network. 
This variable enables or disables dehumidification based on central network 
requirements from the BAS front end 

 

On = 

Dehumidification Authorized 

 

Off = 

Dehumidification Not Authorized 

%RH set

 

Dehumidification setpoint 
Default is 

50 % RH

 

Conditional parameter to Humidity models VTR735xX5x00(X)

 

Used only if dehumidification sequence is enabled: 
Range is: 

30-95% RH  

DehuHyst

 

Dehumidification Hysterisys 
Default is 

5 % RH

 

Conditional parameter to Humidity models VTR735xX5x00(X)

 

Humidity control hysterisys. Used only if dehumidification sequence is enabled: 

 

Range is: 

2 to 20% RH

 

DehuCool

 

Maximum Dehumidification 
Cooling output 
Default is 

100 %  

Conditional parameter to Humidity models VTR735xX5x00(X)

 

Maximum cooling valve position when dehumidification is enabled. This can be 
used to balance smaller reheat loads installed in regards to the capacity of the 
cooling coil. 
Range is: 

20 to 100 %

 

St-By TM 

Stand-by Timer value 
Default 

0.5 hours

 

Time delay between the moment where the PIR cover detected the last movement 
in the area and the time which the Terminal Equipment Controller stand-by mode 
and setpoints become active.  
Range is: 

0.5 to 24.0 hours

 in 0.5hr increments 

Unocc TM 

Unoccupied Timer value 
Default 

0.0 hours

 

Time delay between the moment where the Terminal Equipment Controller toggles 
to stand-by mode and the time which the Terminal Equipment Controller 
unoccupied mode and setpoints become active. 
The factory value or 

0.0 hours:

 Setting this parameter to its default value of 0.0 

hours disables the unoccupied timer. This prevents the Terminal Equipment 
Controller to drift from stand-by mode to unoccupied mode when PIR functions are 
used 
Range is: 

0.0 to 24.0 hours

 in 0.5hr increments 

St-By HT

  

Stand-by heating setpoint 
Default value = 

 69 °F

 

The value of this parameter should reside between the occupied and unoccupied 
heating setpoints and make sure that the difference between the stand-by and 
occupied value can be recovered in a timely fashion when movement is detected 
in the zone.  
Stand-by heating setpoint range is: 

40 to 90 °F ( 4.5 to 32.0 °C )

 

St-By CL

  

Stand-by cooling setpoint limit 
Default value = 

78 °F

 

The value of this parameter should reside between the occupied and unoccupied 
cooling setpoints and make sure that the difference between the stand-by and 
occupied value can be recovered in a timely fashion when movement is detected 
in the zone.  
Stand-by cooling setpoint range is: 

54 to 100 °F ( 12.0 to 37.5 °C )

 

Unocc HT

  

Unoccupied heating setpoint 
Default value = 

 62 °F

 

Unoccupied heating setpoint range is:  

40 to 90 °F ( 4.5 to 32.0 °C ) 

Unocc CL

  

Unoccupied cooling setpoint limit 
Default value = 

80 °F

 

Unoccupied cooling setpoint range is:  

54 to 100 °F ( 12.0 to 37.5 °C )

 

heat max

 

Maximum heating setpoint limit 
Default value = 

90 °F ( 32 °C )

 

Maximum occupied & unoccupied heating setpoint adjustment.  
Heating setpoint range is:  

40 to 90 °F ( 4.5 to 32.0 °C ) 

cool min

 

Minimum cooling setpoint limit 
Default value = 

54 °F ( 12 °C )

 

Minimum occupied & unoccupied cooling setpoint adjustment.  
Cooling setpoint range is:  

54 to 100 °F ( 12.0 to 37.5 °C )

 

Summary of Contents for VTR73 Series

Page 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Page 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Page 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Page 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Page 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Page 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Page 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Page 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Page 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Page 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Page 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Page 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Page 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Page 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Page 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Page 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Reviews: