C or F

 

Sets scale of the Terminal 
Equipment Controller 
Default value = 

°F 

 

°F

 for Fahrenheit scale 

 

°C

 for Celsius scale 

On hotel models, this sets the default value when the Terminal Equipment 
Controller powers up 

%RH disp

 

Local %RH Display 

 
Default value = 

OFF 

Models with Humidity sensor only 

Conditional parameter to Humidity models VTR735xX5x00(X)

 

Enables the display of humidity below the room temperature on the display 

 

 

ON

 = Display %RH 

 

OFF

 = No display of %RH 

Lockout

 

Keypad lockout levels 
Default value = 

0 No lock

 

 

Level 

Occupied temperature 

setpoints 

System mode setting 

Fan mode setting 

Unoccupied Override  

Yes access 

Yes access 

Yes access 

Yes access 

1 Yes 

access

 

Yes access 

Yes access 

No access 

Yes access 

No access 

No access 

Yes access 

Yes access 

No access 

No access 

No access 

No access 

No access 

No access 

Yes access 

No access 

No access 

No access 

No access 

PulsedHt 

Enable pulsed electric heat 
Default Value

 

=

 Off

 

Enables Vdc modulating pulsed electric reheat applications used with SSR’s. 
Only used with VC340xX Relay Pack models 

 

 

Off 

= Regular On-Off control for VC350xE models 

Can be used with 2 pipes & 4 pipes applications 

 

On 

=  10 second pulsed time base modulation for VC340xE models 

Can only be used with 2 pipes 
The VC3400E & VC3404E cannot be used for 4 pipes applications 

Pipe No 

System type installation 
Number of pipes 
Default is: 

4.0 

Pipes 

Defines the type of system installed 

 

2.0 

Pipes

will limit the number of sequences of operation available

 

from 0 to 2

 

Will enable heat/cool operation from the same output 

 

4.0

 Pipes, can access all the sequences of operation from 0 to 4 

Will enable heat/cool operation from different output  

SeqOpera

 Sequence of operation 

Default is: 

Sequence #1

 

Selects the initial sequence of operation required by the installation type and the 
application 

 

System = 2 Pipes 

VR7300A, B C & E Models 

System = 4 Pipes 

VR7300A & C Models only

 

0 = Cooling Only 

Yes access 

Yes access 

1 = Heating Only 

Yes access 

Yes access 

2 =  
Cooling / Heating 

or 

Cooling With Electric Reheat 

Yes access 

 

Cooling With Electric Reheat 

Yes access 

 

Cooling / Heating 

3 = Heating With Electric Reheat 

Yes access 

No access 

4 = Electric Reheat Only 

Yes access 

No access 

 

For 2 Pipe output applications, the system access is also limited if RUI 1 is 
configured for local changeover COS, COC/NC or COC/NC. The current water 
temperature detected by the RUI 1 then limits the system mode available for the 
local configuration or network write. 

For sequence 2 & 3, set PulsedHt to On to enable pulsed electric reheat 
applications with VR7300B & E  

Fan Menu

 

Mode button menu configuration 
Default is: 

Menu #4

 

Menu presented are dependent on model used and sequence of operation 
selected 
Auto Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter  

0 = Low-Med-High 

3

 Speed configuration using 3 fan relays ( L-M-H ) 

1 = Low-High 

2

 Speed configuration using 2 fan relays ( L-H ) 

2 = Low-Med-High-Auto 

3

 Speed configuration with Auto fan speed mode using 3 fan relays ( L-M-H ) 

3 = Low-High-Auto 

2

 Speed configuration with Auto fan speed mode using 2 fan relays ( L-H ) 

4 = On-Auto 

Single

 Speed configuration. Auto is for Fan on demand / On is On all the time 

Summary of Contents for VTR73 Series

Page 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Page 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Page 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Page 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Page 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Page 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Page 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Page 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Page 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Page 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Page 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Page 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Page 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Page 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Page 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Page 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Reviews: