DSP URV: To configure the display URV in the units specified, press
Enter
at the prompt
DSP URV
. Use the
Next
button to toggle between a space or a minus and press
Enter
. Then
use the
Next
button to step through the library of numerical characters to select the desired first
digit, and press
Enter
. Your selection is entered and the second digit flashes. Repeat this
procedure until you have entered your last digit. Then use the next button to move the decimal
point to its desired location and press
Enter
.
Re-ranging an IDP10-A and IDP10-V Transmitter
The IDP10-A and IDP10-V Transmitter can be re-ranged without application of pressure. To
do this in linear mode, just reconfigure EGU LRV and EGU URV. To re-range the transmitter
being used in Square Root mode, perform the following procedure:
1. In Configuration, set
OUTMODE
to
LINEAR
. This is a temporary state.
2. Then configure
EGU LRV
and
EGU URV
, first changing the units in
EGU SEL
if necessary.
3. Save this configuration.
4. Set
OUTMODE
back to your choice of square root mode.
5. Change
EGU SEL
and
DSP URV
if required.
6. Save this configuration.
NOTE
When
OUTMODE
is set in square root mode, the last saved pressure range set by
entering
EGU LRV
and
EGU URV
in linear mode is always maintained.
Summary of Contents for IDP10-A
Page 14: ... 14 98MANALIDP10AV Rev A 8 16 11 ...
Page 16: ... 16 98MANALIDP10AV Rev A 8 16 11 ...
Page 26: ... 26 98MANALIDP10AV Rev A 8 16 11 ...
Page 35: ... 35 98MANALIDP10AV Rev A 8 16 11 ...
Page 37: ... 37 98MANALIDP10AV Rev A 8 16 11 IDP10 A and IDP10 V Calibration ...
Page 40: ... 40 98MANALIDP10AV Rev A 8 16 11 IDP10 A and IDP10 V Configuration ...