47
P 50
Boiler primary pump man/auto
Setting of the pump control type. Man – manual pump run, Auto – automatic pump run according to
current requirements.
Value 0 – Man
Value 1 – Auto
P 51
Boiler primary pump off/on
Primary pump switched on in case we have selected value 0 – Man on the line no.50.
Value 0 – Switched off
Value 1 – Switched on
Note: In case value 0 is selected in parameter P 50 it is necessary to select here the value 1. If it be to
the contrary the pump will not be active.
P 52
Boiler primary pump slowing-down
[min.]
We select boiler pump slowing-down on this line.
P 53
Boiler primary pump switch-on temperature
[
o
C]
Once this set boiler temperature has been achieved the boiler primary pump will switch on. The pump
will switch off once the temperature has dropped by 5 °C below the temperature set for pump
switching-on.
P 54
Day of boiler primary pump spinning
On the determined day the pump spinning will be done at 12:00 h for 30 sec.
Value 1 - 7 – corresponds to days from Monday to Sunday
Value 0 – primary pump spinning is not active
Value 8 – primary pump spinning is active every day
Note: If at this time the pump is working the function is not active
P 55
Heating circuit pump man/auto
Setting of pump control type. Man – pump manual run, Auto – pump automatic run according to current
requirements.
Value 0 – Man
Value 1 – Auto
P 56
Heating circuit pump off/on
Circuit pump switched on in case we have selected value 0 – Man on the line no. 55.
Value 0 – Switched off
Value 1 – Switched on
Note: In case value 0 is selected in parameter P 55 it is necessary to select here the value 1. If it be to
the contrary the pump will not be active.
P 57
Heating circuit pump slowing-down
[min.]
We select heating circuit pump slowing-down on this line.
P 58
Day of heating circuit pump spinning
On the determined day the pump spinning will be done at 12:00 h for 30 sec.
Value 1 - 7 – corresponds to days from Monday to Sunday
Value 0 – TO pump spinning is not active
Value 8 – TO pump spinning is active every day
Note: If at this time the pump is working the function is not active
P 59
Warm water pump man/auto
Setting of type of pump control; Man –pump manual run, Auto – pump automatic run according to the
current requirements.
Value 0 – Man
Value 1 – Auto
Attention! The value 0 is only designed for HW pump service testing.
The permanent setting of pump manual run can result in water heater chilling. Therefore keep the set
value1.
P 60
Warm water pump off/on
Warm water pump switched on in case we have selected value 0 – Man on the line no. 59.
Value 0 – Switched off
Value 1 – Switched on
Note: In case the value 0 is selected in P 59 parameter it is necessary to select here the value 1. If it
be to the contrary the pump will not be active.
P 61
Warm water pump slowing-down
[min.]
We select warm water pump slowing-down on this line