37
Tab. no. 7 Parameters – Mixing heating circuit
Parameter
Description
Units
Set by the
manufacturer
Range
Resolution
P 1
Current outside temperature
[
o
C]
-
-20 … 50
0,1
P 2
Current boiler temperature
[
o
C]
-
5 … 100
0,1
P 3
Current heating circuit temperature
[
o
C]
-
5 … 100
0,1
P 4
Desired heating circuit temperature
[
o
C]
-
0 … 80
0,1
P 6
Desired boiler temperature in case of HW
heating
[
o
C]
-
0 … 75
1
P 7
Current warm water thermostat status
-
0 … 1
1
P 8
Current feeder temperature
[
o
C]
-
5 … 100
0,1
P 9
Current space temperature
[
o
C]
-
0 … 40
0,1
P 10
Current position of three-way mixing valve
[%]
-
0 … 100
0,1
P 11
Desired boiler temperature
[
o
C]
-
20 … 85
0,1
P 12
Current ventilator output
[%]
-
0 … 100
0,1
P 15
Faults
-
0 … 15
P 19
Parallel shift in the heating curve
[
o
C]
0
-10 … 10
1
P 20
Fuel type
1
1 … 3
1
P 21
Slope of heating curve
1,5
0,1 … 4
0,1
P 22
Ventilator output when making fire
[%]
50
1 … 100
1
P 23
Minimum boiler temperature
4 sect./5 – 7 sect.
[
o
C]
50/60
20 … 70
0,1
P 24
Type of requirement (auto/fixed)
0
0 … 1
1
P 25
Boiler hysteresis
[
o
]
3
1 … 5
0,1
P 26
Maximum feeder temperature
[
o
C]
90
85 … 95
1
P 27
Boiler heating deficiency
[min.]
30
10 … 60
1
P 28
QAA position
2
1 … 2
1
P 40
Heating circuit off/on
1
0 … 1
1
P 41
Boiler temperature increase from the
heating circuit
[
o
C]
5
0 … 20
1
P 42
Warm water off/on
1
0 … 1
1
P 43
Boiler temperature increase from HW
[
o
C]
15
5 … 20
1
P 50
Boiler primary pump man/auto
1
0 … 1
1
P 51
Boiler primary pump off/on
-
0 … 1
1
P 52
Boiler primary pump slowing-down
[min.]
5
0 … 60
1
P 53
Boiler primary pump switch-on temperature
[
o
C]
55
20 … 60
1
P 54
Day of boiler primary pump spinning
5
0 … 8
1
P 55
Heating circuit pump man/auto
1
0 … 1
1
P 56
Heating circuit pump off/on
-
0 … 1
1
P 57
Heating circuit pump slowing-down
[min.]
3
0 … 60
1
P 58
Day of heating circuit pump spinning
5
0 … 8
1
P 59
Warm water pump man/auto
1
0 … 1
1
P 60
Warm water pump off/on
-
0 … 1
1
P 61
Warm water pump slowing-down
[min.]
3
0 … 10
1
P 62
Day of warm water pump spinning
5
0 … 8
1
P 70
Outside temperature reset
0
0 … 1
1
P 71
Space hysteresis
[
o
C]
0,5
0,1 … 5
0,1
P 72
Space effect
[%]
20
0 … 100
1
P 76
Minimum heating circuit temperature
[
o
C]
30
20 … 50
1
P 77
Maximum heating circuit temperature
[
o
C]
80
30 … 90
1
P 80
Building constant
[h]
10
1 … 50
1
P 81
Temperature ECO
[
o
C]
-3
-5 … 5
1
P 82
ECO automatics passive/active
-
0 … 1
1
P 83
Temperature summer/winter
[
o
C]
17
8 … 35
1
P 84
Constant summer/winter
[h]
50
1 … 100
1
P 85
Current status summer/winter
-
0 … 1
1
P 86
Heating system
3
0 … 3
1
P 87
HC antifreeze protection off/on
1
0 … 1
1
P 88
Servo overruntime
[s]
120
10 … 1800
1
P 100
Setting the day of time schedule for HC
1
0 … 7
1
P 101
First HC period switched on
[h:min.]
6:00
0:00 … 23:59
1 min.
P 102
First HC period switched off
[h:min.]
22:00
0:00 … 23:59
1 min.
P 103
Desired space temperature in the first
period
[
o
C]
21
10 … 30
0,1