inStALLAtiOn 

Continued

Figure 19 - Remote Control Receiver 

Remote.
Control.
Receiver

Convertible.
Gas.Valve

GAS SUPPLY TESTING

NOTICE:  This  section  is  in-

tended as a guide for qualified 

technicians installing gas to the 

appliance.

 WARNING: Do not connect 

appliance before pressure test

-

ing gas piping. Damage to gas 

valve may result and an unsafe 

condition may be created.

The.appliance.and.its.individual.shutoff.valve.
must. be. disconnected. from. the. gas. supply.
piping.system.during.any.pressure.testing.of.
that.system.at.test.pressures.in.excess.of.1/2.
psig.(3.5.kPa)..
The.appliance.must.be.isolated.from.the.gas.
supply.piping.system.by.closing.its.individual.
shutoff.valve.during.any.pressure.testing.of.
the.gas.supply.piping.system.at.test.pressures.
equal.to.or.less.than.1/2.psig.(3.5.kPa).
The.gas.control.valve.is.secured.underneath.

the firebox. Two 1/8" ports are provided  on 

the.gas.control.valve.for.pressure.test.gauge.
connections.(see.Figure.20).

Figure 20 - Gas Control Valve

ON/OFF.

Knob

Pilot.Adjustment

Inlet.
Pressure Outlet.

Pressure

Flame.

Adjustment Knob

Pilot.Gas.Line.

Do Not Kink

To.Pilot.
Burner

To.Main
Burner

GAS LINE HOOK-UP

  WARNING:  Gas  line  hook-

up should be done by your gas 

supplier  or  a  qualified  service 

person.

 WARNING: Before you pro

-

ceed, make sure your gas supply 

is OFF.

An.equipment.shutoff.valve.has.been.included.

in the fireplace's gas supply system. Consider 

installing.an.extra.shutoff.valve.outside.the.ap-
pliance’s.enclosure.(check.local.codes),.where.
it.can.be.accessed.more.conveniently.with.a.
key.through.a.wall.as.shown.in.Figure.21.
In.conformance.with.local.codes,.route.a.1/2".
NPT.gas.line.towards.the.appliance.coming.in.
from.either.the.bottom,.left.or.right.side.of.the.

fireplace (see Figure 22, page 14).

Figure 21- Typical Exterior Wall Gas 

Shutoff Installation

Key

Extension

Shutoff.
Valve

The.remote.control.receiver.is.factory.wired.
and.connected.to.the.convertible.gas.valve.
as.shown.in.Figure.19.

Summary of Contents for CD32M-B

Page 1: ...o not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier...

Page 2: ...turers instructions and the Manufactured Home Construction and Safety Stan dard Title 24 CFR Part 3280 in the United States or the Mobile Home Standard CAN CSA Z240 MH Series in Canada This fireplace...

Page 3: ...stallation is the most important step in ensuring safe and continuous operation of the fireplace Consult the local building codes as to the particular requirements concerned with the installation of a...

Page 4: ...ts that have been submerged under water Pre Installation Preparation CAUTION Do not block required air spaces with insula tionoranyothermaterial Donot obstruct the effective opening of the appliance w...

Page 5: ...which could cause a fire WARNING Horizontal sec tions of this vent system require a minimum clearance of 2 from the top of the pipe and 1 mini mum to the sides and bottom Vertical sections of this sys...

Page 6: ...reater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally L cleara...

Page 7: ...n of any component part not manufactured or approved by DESA Installation other than as instructed by these instructions NOTICE AllVexardirectventfire places must use DESA 5 8 pipe components and term...

Page 8: ...an offset is necessary in the attic to avoid obstruction it is important to sup port the vent pipe every 3 ft to avoid excessive stress on the elbows and possible separation see Figure 8 Installation...

Page 9: ...on Slide Ring Over Elbow to Complete Connection CD32 Series Vertical V Minimum CD36 Series Vertical V Minimum CD42 Series Vertical V Minimum Required Vertical Pipe Horizontal H Maximum 401 2 431 2 461...

Page 10: ...wing configurations show the minimum vertical rise requirements for a horizontal system using two 90 elbows Venting with Two 90 Elbows Figure 12 Horizontal Termination Configuration for Venting Using...

Page 11: ...ne down from the ceiling to the position of the fireplace exit flue Mark the center point where the vent will penetrate the ceiling Drill a small locating hole at this point Drop a plumb line from the...

Page 12: ...Round High Wind Termination Shown Note Install restrictor into inner collar of fireplace as shown Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical...

Page 13: ...o 1 8 ports are provided on the gas control valve for pressure test gauge connections see Figure 20 Figure 20 Gas Control Valve ON OFF Knob Pilot Adjustment Inlet Pressure Outlet Pressure Flame Adjust...

Page 14: ...ation Continued Figure 22 Gas Line Routing Gas Routing Right Side Not Shown Side of Fireplace Front Face Figure 23 Sediment Trap Sediment Trap Not Supplied Incoming 1 2 Gas Line Permitted By Local Cod...

Page 15: ...ket forward so you are able to access back of remote receiver 3 Locate battery clip mounted on back of receiver Slide a 9 volt alkaline battery not included through clip see Figure 27 4 Attach termina...

Page 16: ...log 2 large front log over pins on grate see Figure 31 Figure 30 Installing Log 1 CD36M B Series Shown Figure 31 Installing Log 2 CD36M B Series Shown 1 2 CD32M Log 1 Placement 3 Figure 32 Installing...

Page 17: ...2 and 3 see Figure 38 5 Place log 5 top log onto right pin of front log 2 and smooth surface of rear log 3 Make sure it is seated properly see Figure 39 6 Place log 6 left log on left pin of front log...

Page 18: ...erial may be used as facing glass tile brick etc as long as the proper clearances are observed see Clear ances to Combustibles page 4 Louvered openings must not be obstructed and upper and lower panel...

Page 19: ...2 Burner Flame Patterns CORRECT INCORRECT CLOSE SHUTTER INCORRECT OPEN SHUTTER Short Sharp Blowing Flame Long Blue Flame with Yellow Tips Long Uneven Yellow Flame Tube Burner Pan Burner Model NG LP NG...

Page 20: ...Operating Fireplace operation guidelines When used for the first time the fireplace may emit a slight odor for about 16 to 24 hours This is normal and is due to the cur ing of the logs and the burn in...

Page 21: ...s 3 Undo latches located on top and bottom of firebox and swing door to fully open position 4 Carefully remove log set and ember mate rial from burner and place them aside in a safe place 5 Replace ma...

Page 22: ...ith kit Tighten screws securely approximately 25 in lb See Figure 48 3 Install identification label enclosed with gas valve regulator to valve body where it can easily be seen see Figure 48 WARNING Th...

Page 23: ...inge ment on thermocouple 3 Ensure connection between valve and thermocouple are tight and secure 4 Check thermocouple with millivolt meter Take reading at thermocouple terminals of gas valve with rem...

Page 24: ...m 119212 01B 24 6 7 19 18 10 23 24 34 2 17 8 21 2 21 6 21 4 21 5 21 3 21 1 1 9 16 3 14 4 20 15 5 15 13 11 35 36 22 37 39 38 25 12 26 30 27 28 29 33 31 32 Illustrated Parts Breakdown Models CD32M B and...

Page 25: ...9009 01 Base Log Log 3 1 21 4 109406 01 109008 01 Crossover Log Log 4 1 21 5 109405 01 107348 01 Left Top Log Log 5 1 21 6 109408 01 107347 01 Right Top Log Log 6 1 22 11102 11102 Screw 8 32 x 3 8 PPH...

Page 26: ...com 119212 01B 26 Illustrated Parts Breakdown Model CD42M A 37 23 41 42 38 22 39 32 31 33 28 26 25 29 24 34 35 40 36 30 27 28 6 7 19 18 10 12 2 11 17 8 20 1 4 13 16 3 14 15 5 15 9 212 21 3 21 6 21 7 2...

Page 27: ...Crossover Log Log 4 1 21 5 109399 01 Top Center Log Log 5 1 21 6 109400 01 Top Left Log Log 6 1 21 7 109401 01 Top Right Log Log 7 1 22 11102 Screw 8 32 x 3 8 PPH Zinc 2 23 11105 Screw 10 x 1 2 Zinc...

Page 28: ...A2 Only Pilot Gas Line Wireway GND BLK WHT GRN Incoming 120V AC Fuse Box or Breaker Connectors Not Supplied Field Wire N O SW Specifications CD32M B Gas Rate Natural 12 000 18 000 Btu hr Gas Rate Pro...

Page 29: ...1 CD32M B 108719 01 CD36M B Series 108455 01 CD42M A Series Glass door Assembly 108892 01 CD32M B 110994 01 CD36M B Series 108328 01 CD42M A Series Burner Orifices CD32M B NG Orifice 47 104506 25 LP O...

Page 30: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 31: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 32: ...2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 www desatech com NOT A UPC 119212 01 Rev B 02 07 119212 01...

Reviews: